3. INSTALLATION OF DISCHARGER
Conditions of use:
• Operating /Storage temperature: 5°C to 45°C
• Relative humidity: less than 75%
A
__________________________________________________________________________________________________________________________________________________
Page 7/27
WARNING !
The discharger can be installed by qualified personnel only!
To avoid the risk of injuries, the user is not allowed to open the cabinet.
Always refer to qualified electricians for installation and service operations.
WARNING !
To prevent fire or shock hazard, do not expose the discharger to rain or moisture.
Do not use the e discharger in presence of flammable gas, because it can generate sparks!
Do not install the discharger near flammable materials.
CAUTION !
Before to install the discharger:
Check that the discharger input voltage (V) is identical to your AC power supply voltage.
Check that the discharger max input power (KVA) is available from your AC power supply.
WARNING !
To reduce the risk of fire, the discharger must be installed on a
floor of non-combustible material.
If this is not possible, a floor plate of at least 1,6mm steel extended
at least 150mm beyond the discharger on all sides must be installed.