EasyManua.ls Logo

Baumuller BUM 62 T - Page 29

Baumuller BUM 62 T
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
Mono Power Unit BUM 62 T 29
Baumüller Nürnberg GmbH 5.99009.03
Screening
y The screen is effective against magnetic fields when it is connected to ground at both ends.
With electrical fields, the screening is effective if the screen is connected to ground at one end.
For electrical or magnetic fields with high frequencies (depending on the cable length), always apply
the screen at both ends because of the linkage (electromagnetic field).
If you apply the screen to ground at both ends, the cable does not leave the screening ”system
housing”.
y If you connect cable screens to ground at both ends, the effect of earth loops (potential difference
on the ground system) cannot be excluded totally. However, these are very rare if you observe the
measures of the above chapters ”Cabling” and ”Grounding”.
The HF connection of a screen to ground can also be capacitive. This prevents low-frequent noise
caused by earth loops.
Screen cables passing through different EMC areas must not be separated at the terminals,
otherwise the screening would be reduced considerably. They should be led to the next module
without interruption.
The screen connection should be of low impedance and over a large surface. Cable tails with a
length of only 3 cm (1 cm wire = 10 nH) reduce the screening of up to 30 dB when noise occur in the
MHz range!
NOTE
The screen braid must have a coverage of at least 85%.
The following cables have a particularly high interference potential:
Motor cable
Cable to external regenerative resistors
Cable between mains filter and converter

Related product manuals