Commissioning
Mono Power Unit BUM 62 T 57
Baumüller Nürnberg GmbH 5.99009.03
provided that the mains failure time > 0 seconds has been set. Refer to ”Mains failure time” in the
controller description)
y Monitoring function of short-circuit regenerative circuit output
The connection for the external regenerative circuit is monitored.
If the monitoring function recognizes a short-circuit at the connection for the external regenerative
circuit, the message ”Short-circuit regenerative circuit” is generated. This message is stored and the
message ”Supply part ready” is cleared.
w
WARNING
If you enable an automatic start of the drive, you cause a severe danger of the operating personnel.
If a enable an automatic start of the drive, you must provide a protection on the machine side!
w
WARNING
A short-circuit of the regenerative circuit may destroy the unit.