Page #41 background image
Mounting and wiring
EK110x, EK15xx 41Version: 3.6
Additional installation instructions
For terminals with enhanced mechanical load capacity, the following additional installation instructions apply:
The enhanced mechanical load capacity is valid for all permissible installation positions
Use a mounting rail according to EN 60715 TH35-15
Fix the terminal segment on both sides of the mounting rail with a mechanical fixture, e.g. an earth
terminal or reinforced end clamp
The maximum total extension of the terminal segment (without coupler) is:
64 terminals (12 mm mounting with) or 32 terminals (24 mm mounting with)
Avoid deformation, twisting, crushing and bending of the mounting rail during edging and installation of
the rail
The mounting points of the mounting rail must be set at 5 cm intervals
Use countersunk head screws to fasten the mounting rail
The free length between the strain relief and the wire connection should be kept as short as possible. A
distance of approx. 10 cm should be maintained to the cable duct.