21
AF120(-S) US, AF230(-S) US
On/Off, Spring Return Fail-Safe, 120 or 230 VAC
Accessories
AV 10-18 Shaft extension
IND-AF2 Damper position indicator
K4 US Universal clamp for 3/8” to 3/4” shafts
K4-1 US Universal clamp for up to 1.05” dia jackshafts
KH-AF Crankarm for up to 3/4” round shaft (Series 2)
KH-AF-1 Crankarm for up to 1.05” jackshaft (Series 2)
KH-AFV V-bolt kit for KH-AF and KH-AF-1
Tool-06 8mm and 10 mm wrench
ZG-HTR Thermostat/Heater Kit
ZDB-AF2 US Angle of rotation limiter
ZG-100 Universal mounting bracket
ZG-101 Universal mounting bracket
ZG-102 Multiple actuator mounting bracket
ZG-106 Mounting bracket for Honeywell
®
Mod IV replacement or
new crankarm type installations
ZG-107 Mounting bracket for Honeywell
®
Mod III or Johnson
®
Series 100 replacement or new crankarm type installations
ZG-108 Mounting bracket for Barber Colman
®
MA 3../4..,
Honeywell
®
Mod III or IV or Johnson
®
Series 100
replacement or new crankarm type installations
ZG-AF US Crankarm adaptor kit for AF/NF
ZG-AF108 Crankarm adaptor kit for AF/NF
ZS-100 Weather shield (metal)
ZS-150 Weather shield (polycarbonate)
ZS-260 Explosion-proof housing
ZS-300 NEMA 4X housing
NOTE: When using AF120/230 US and AF120/230-S US actuators,
only use accessories listed on this page.
For Actuator Wiring Information and Diagrams, Please See Belimo Wiring Guide (pg 349).
Typical Specification
On/Off spring return damper actuators shall be direct coupled type
which require no crankarm and linkage and be capable of direct
mounting to a jackshaft up to a 1.05” diameter. The actuators must be
designed so that they may be used for either clockwise or
counterclockwise fail-safe operation. Actuators shall have a manual
positioning mechanism accessible on its cover. Actuators shall use a
brushless DC motor and be protected from overload at all angles of
rotation. Run time shall be constant and independent of torque. If
required, 2 SPDT auxiliary switches shall be provided with one switch
having the capability of being adjustable. Actuators must be constructed
to meet the requirement for Double Insulation so an electrical ground
connection is not required to meet agency listings. Actuators shall be
UL Approved and CSA certified, have a 5 year warranty, and be
manufactured under ISO 9001 International Quality Control Standards.
Actuators shall be as manufactured by Belimo.
Wiring Diagrams
1
Provide overload protection and disconnect as required.
2
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3
No ground connection is required.
4
For end position indication, interlock control, fan startup, etc.,
AF120/240-S US incorporates two built-in auxiliary switches: 2 x
SPDT, 7A (2.5A) @250 VAC, UL Approved, one switch is fixed at +5°,
one is adjustable 25° to 85°.
Meets cULus requirements without the need of an electrical ground
connection.
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
W004_08
On/Off wiring for AF120-S US and AF230-S US
W003_08
On/Off wiring for AF120 US and AF230 US
K20901 - 01/09 - Subject to change. © Belimo Aircontrols (USA), Inc.