Dimensions (Inches [mm]
)
CCW
CCW
CCW
CCW
CW
CW
CW
CW
I
nstallation Instruction
s
Quick-Mount Visual Instructions for Mechanical Installatio
n
Quick-Mount Visual Instructions
1
. Rotate the dam
p
er to its fail-safe
p
osition
.
If the shaft rotates counterclockwise, mount the “CCW” side of the actuator out
.
If it rotates clockwise, mount the actuator with the “CW” side out.
2
. If the universal clamp is not on the correct side of the actuator, mount it onto the correct side
.
3.
S
lide the actuator onto the shaft and tighten the nuts on the V-bolt with a 10mm wrench to 6-8 ft-lb of torque
.
4. Slide the anti-rotation strap under the actuator so that it en
g
a
g
es the slot at the base of the actuator. Secure the strap to the duct work with #8 self-tappin
g
screws.
NO
TE: Read the “
S
tandard Mountin
g
instructions, on the next pa
g
e, for more detailed information
.
min. 3 1/2” [90]
min. 3/4” [20]
.2
.8
CCW CW