13
5) The gate leaves should open.
In the negative, the operation wires of the motor should be inverted by turning motor 1 connector by 180° and inverting wires
26<>28 for motor M2.
6) Select the motor which should start the operation first in the opening phase by using the MINV logics, see Fig.4.
7) Carry out an autoset procedure (see SET menu).
PROGRAMMING
The programming of the various functions of the control unit is carried out using the LCD display on the control unit and setting the
desired values in the programming menus described below.
The parameters menu allows you to assign a numerical value to a function, in the same way as a regulating trimmer.
The logic menu allows you to activate or deactivate a function, in the same way as setting a dip-switch.
Other special functions follow the parameters and logic menus and may vary depending on the type of control unit or the software
release.
USE OF PROGRAMMING KEYS
Press <PG> key to gain access to the Main Menu (PAR>>LOG>>RADIO>>...). These keys can be selected by pressing + and
– keys.
Select the Main menu with <PG> key to enter the desired Function Menu .
• If <+> is pressed, the Function Menu can be scrolled from top to bottom.
• If <-> is pressed, the Function Menu can be scrolled from bottom to top.
• If <PG> key is pressed, presetting to be modified can be entered.
• The preset values can be modified by using <+> and <-> keys.
• The value is programmed if <PG> key is pressed again. The word “PRG” appears on the display.
See paragraph “Programming Example”.
NOTES:
Simultaneously pressing <+> and <-> from inside a function menu allows you to return to the previous menu without making any
changes.
Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values.
After waiting 30s the control unit quits programming mode and switches off the display.
Pressing <-> with the display turned off means an impulse of P.P.
PARAMETERS, LOGIC AND SPECIAL FUNCTIONS
The tables below describe the individual functions available in the control unit.
MENU FUNCTION
MIN-MAX-(Default)
MEMO
PARAMETERS
TCA
Automatic closing time. Active only with logic “TCA”=ON.
At the end of the set time the control unit orders a closing manoeuvre.
1-240-(40s)
tsm1
Braking value of motor 1. The values indicate the brake percentage of
the gate leaf (25%-50%-75%-100%) compared to the total opening/
closing.
25-100-(50)
tsm2
Braking value of motor 2. The values indicate the braking percentage
of the gate leaf (25%-50%-75%-100%) compared to the total opening/
closing.
25-100-(50)
TPED
Operating time of pedestrian gate leaf
Values which can be preset are:
25: 25% opening
50: 50% opening
100: 100% opening
25-100-(100)
PMo1
The torque applied to motor 1 during the opening phase is adjusted.* 1-99-(20%)
PMC1
The torque applied to motor 1 during the closing phase is adjusted.* 1-99-(20%)
PMo2
The torque applied to motor 2 during the opening phase is adjusted.* 1-99-(20%)
PMc2
The torque applied to motor 2 during the closing phase is adjusted.* 1-99-(20%)
TDMo
Mot.2 opening delay time.
Regulates the delay time of motor 2 on opening with respect to motor 1
0-15-(2s)
TDMC
Mot.1 closing delay time
Regulates the delay time of motor 1 on closing with respect to motor 2
0-40-(3s)
SLD1
It regulates the motor 1 speed during braking. The value is expressed in
percentage with respect to normal operating speed.
40-99 (50)
SLD2
It regulates the motor 2 speed during braking. The value is expressed in
percentage with respect to normal operating speed.
40-99 (50)