14
PARAMETERS
Pso1
The torque applied to motor 1 during braking in the opening phase is ad-
justed *
1-99-(20%)
Psc1
The torque applied to motor 1 during braking in the closing phase is ad-
justed *
1-99-(20%)
Pso2
The torque applied to motor 2 during braking in the opening phase is ad-
justed *
1-99-(20%)
Psc2
The torque applied to motor 2 during braking in the closing phase is ad-
justed *
1-99-(20%)
TLS
It adjusts the operating time of the service light when the “Service Light”
logics is preset to ON and the “2nd radio channel” logics is preset to
OFF
2s-180s-(60s)
* WARNING: An incorrect setting of these parameters may result in an hazard. Comply with regulations in force!
To check the torque applied to the various phases of the operation, proceed as follows:
With switched-off display and moving gate leaves, press and keep the <+> key pressed
Two figures separated by a dot are displayed (e.g. 52.55), the first two figures indicate the torque applied to motor 1, while the
last two the torque applied to motor 2.
MENU FUNCTION
ON-OFF-(Default)
MEMO
LOGIC
TCA
Enables or disables automatic closing
On: automatic closing enabled
Off: automatic closing disabled
(ON)
IbL
Enables or disables condominium function.
On: condominium function enabled. The step-by-step impulse or transmitter
impulse has no effect during the opening phase.
Off: condominium function disabled.
(OFF)
SCL
Enables or disables rapid closing
On: rapid closing enabled. With the gate open or in the opening phase the
intervention of the photocell causes automatic closing after 3 s. Active only
with TCA:ON.
Off: rapid closing disabled.
(OFF)
PP
Selects the operating mode of the ”Step by step button” and of the
transmitter.
On: Operation: OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >
(OFF)
PRE
Enables or disables pre-blinking.
On: Pre-blinking enabled. Blinking is activated 3s before the motor starts.
Off: Pre-blinking disabled.
(OFF)
SERL
The “service light” function is enabled or disabled on terminals (9-10)
On: output, enabled as “Service light”. This output is activated at the beginning
of each operation and remains activated for the time preset by parameter TLS.
Off: output, enabled as “Open gate light”.
This function is not enabled if the “2°Ch radio” logics is preset to ON.
OFF
2ch
The second radio channel is enabled or disabled on terminals (9-10).
On: “2
nd
radio channel” output is enabled.
Off: “2
nd
radio channel” output is disabled. The output to terminals is activated
as “Service light” if SERL=On, or as SCA if SERL=Off.
If this function is preset to On, any presetting of the SERL logics will be ig-
nored.
(OFF)
CLOC
The OPEN Input mode is preset.
On: OPEN Input, with CLOCK function.
To be used as connection to timer for timed opening/closing. (Closed contact:
gate open. Open contact: normal operation).
Off: OPEN input, with OPEN function.
This function is activated only if the OPCL logics=ON
(OFF)
OPCL
The Step-by-Step and Pedestrian input modes is selected.
On: Input to terminal 18 activated as OPEN. Input to terminal 17 is activated
as Closed.
Off: Input to terminal 18 activated as Step-by-Step. Input to terminal 17 acti-
vated as Pedestrian.
(OFF)