Switch mode, single-phase, sine-wave Inverter
Product line TEBEVERT
August 8, 2005 - DTL 15/21 No. 4219en R2
Load fuse: The short circuit current can blow
slow fuses with
1
/
3
of the nominal
current rating.
Radio interference degree: Class B (EN 55022)
Switch-over device: Mechanical contactor
Switching times: 100 ms
Switching thresholds of the input voltage monitoring:
3
Setting parameter
Default settings
Lower switch-off threshold U1 20.4 V
Switch-on threshold U2 24.5 V
Switch-on threshold U3 28.8 V
Upper switch-off threshold U4 30.0 V
Rated input voltage 48 V DC
Lower switch-off threshold U1 40.8 V
Switch-on threshold U2 49.0 V
Switch-on threshold U3 57.6 V
Upper switch-off threshold U4 60.0 V
The inverter can be switched on only when the input voltage UDC U2.