EasyManua.ls Logo

Bentone bg 300 - TECHNICAL DATA; Output Range

Bentone bg 300
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CAPACITY CHART ACCORDING TO
EN 676
Gas fittings
2
) Motor Ignition transformer
Natural gas, LPG Town gas 1-phase, 0,18 kW, Primary 230 V, 1, A
1" 1½" 2 800 r/m, 230 V Secondary 8 000 V
TECHNICAL DATA
Type designation BG 300
1
) Calorific value:
Natural gas 10 kWh/Nm
3
LPG 26 kWh/Nm
3
2
) Dimension and capacity depen-
ding on gas quality and availa-
ble pressure
Type Capacity Gas volume at a min. Gas volume at a max Max. Inlet Rated inlet pressures
kW ouput Nm
3
/h
1
) output Nm
3
/h
1
) pressure mbar mbar
Natural gas/LPG Natural gas LPG Natural gas LPG Natural gas LPG
300 60-190 6 2,3 19 7,3 100 20 20
(4,6 kg/h) (14,8 kg/h)
2
) Town gas
2
) Town gas
2
) Town gas
2
) Town gas
172 215 11 00-02
Length of burner tube Measure A Measure B
Standard 145 125 ø120
Long design 245 225 ø120
Town gas 172 155 ø140
The above dimensions are max. measurements. Depending on the compo-
nents used, the measurements may vary.
OUTPUT RANGE
DIMENSIONS
170
B
A
460
ø108
372
100
220
380