8
CIAO GREEN C.S.I.
At this point the boiler will automatically start and the red lamp switches on in green.
N.B. If the attempt to reset the appliance does not activate operation, contact the Technical Assistance Service.
4.2 Switching off
Temporary switch-off
In case of absence for short periods of time, set the mode selector (g. 32) to (OFF).
In this way (leaving the electricity and fuel supplies enabled), the boiler is protected by the following systems:
Anti-frost device: when the temperature of the water in the boiler falls below 5°C, the circulator and, if necessary, the burner are activated at minimum
output levels to bring the water temperature back to the values for safety (35°C). During the anti-frost cycle, the symbol (g. 36) appears on the digital
monitor.
Circulator anti-blocking function: an operation cycle is activated every 24 hours.
Switching off for long periods
In case of absence for long periods of time, set the mode selector (g. 32) to (OFF). Turn the main system switch OFF. Close the fuel and water taps
of the heating and domestic hot water system. In this case, anti-frost device is deactivated: drain the systems, in case of risk of frost.
4.3 Light signals and faults
BOILER STATUS
DISPLAY
RED LED YELLOW LED GREEN LED
TYPES OF
ALARMS
Off status(OFF) OFF
ashing 0.5 on/
3.5 off
None
Stand-by -
ashing 0.5 on/
3.5 off
Signal
ACF alarm lockout module
A01
on Denitive lockout
ACF electronics fault alarm
Limit thermostat alarm
A02
ashing 0.5 on/
0.5 off
Denitive lockout
Tacho fan alarm
A03
on Denitive lockout
Water pressure switch alarm
A04
on on Denitive lockout
NTC domestic water fault A06
ashing 0.5 on/
0.5 off
ashing 0.5 on/
0.5 off
Signal
NTC heating outlet fault
A07
on
Temporary stop
Heating outlet probe overtemperature
Temporary then
denitive
Outlet/return line probe differential alarm Denitive lockout
NTC heating return line fault
A08
on
Temporary stop
Heating return line probe overtemperature
Temporary then
denitive
Outlet/return line probe differential alarm Denitive lockout
Cleaning the primary heat exchanger
A09
ashing 0.5 on/
0.5 off
ashing 0.5 on/
0.5 off
Signal
NTC ue gases fault Temporary stop
Flue gases probe overtemperature on Denitive lockout
False ame
A11
ashing 0.2 on/
0.2 off
Temporary stop
Low temperature system thermostat alarm
A77
on Temporary stop
Temporary pending ignition
ashing 0.5 on/
0.5 off
Temporary stop
Water pressure switch intervention
ashing 0.5 on/
0.5 off
Temporary stop
Calibration service
ADJ
ashing 0.5 on/
0.5 off
ashing 0.5 on/0.5
off
ashing 0.5 on/
0.5 off
Signal
Calibration installer
Chimney sweep
ACO
ashing 0.5 on/0.5
off
Signal
Vent cycle
ashing 0.5 on/
1.0 off
ashing 0.5 on/1.0
off
ashing 0.5 on/
1.0 off
Signal
Preheating active function on Signal
Preheating heat request
ashing
Signal
External probe presence Signal
Domestic water heat request 60
°C
Signal
Heating heat request 80
°C
Signal
Antifreeze heat request Signal
Flame present on Signal