If the reset attempts do not activate the boiler, contact the Technical Assistance
Centre.
For fault E041
If the pressure drops below the safety threshold of 0.3 bar the boiler displays the fault code
<<E041 water transducer load the system>>
for a transitional time of
30sec.
DAY
When the transitional time has nished, if the fault persists the fault code E040 is displayed
.
When the boiler has fault E040 manual loading should be carried out using the lling tap
(
A
)
until
the pressure is between 1 and 1.5 bar
. Then press RESET.
C
lose the lling tap, making sure to hear the mechanical snap
.
A
t the end of the procedure, proceed with the automatic vent cycle as described in the section
"3.15 Filling the heating system and eliminating air".
b
I
f the drop in pressure is very frequent, contact the Technical Assistance Centre
.
For fault E060
The boiler is working normally, but does not provide any stability of the domestic hot water
temperature that, in any event, is supplied at a temperature of around 50°C. The intervention
of the Technical Assistance Service is required.
For fault E091
The boiler has an auto-diagnostic system which, based on the total number of hours in
certain operating conditions, can signal the need to clean the primary exchanger (alarm
code E091).
Once the cleaning operation (made with special kit supplied as an accessory) it is necessary
to reset to zero the total hour meter following procedure indicated below:
access the technical parameters as explained in the section
"3.20 Access to the
parameters"
select the CONF menu and then EXHAUST PROBE RESET with the keys and
set the parameter to 1 conrming the selection with
Enter
.
NOTE: The meter resetting procedure should be carried out after each in-depth
cleaning of the primary exchanger or if this latter is replaced.
The total hours can be veried in the following way:
access the INFO menus as indicated in the paragraph "4.21 INFO menu" at EXHAUST
PROBE RESET to display the value of the ue gases probe meter.
Boiler faults list
ERROR
CODE
FAULT RED LED GREEN LED RED and GREEN LED
DESCRIPTION OF
ALARM TYPE
E010 ame lockout/ACF electronic fault ON denitive
E011 extraneous ame
ashing 0,2 sec. ON/0,2 sec. OFF
transitional
E020 limit thermostat
ashing 0,5 sec. ON/0,5 sec.
OFF denitive
E030 fan fault ON denitive
E040 water transducer – load system ON denitive
E041 water transducer – load system
ashing 0,5 sec. ON/0,5 sec. OFF
transitional
E042 water pressure transducer fault
ON
denitive
E060 domestic hot water probe fault
ashing 0,5 sec. ON/0,5 sec. OFF
transitional
E070
ow sensor fault
ow sensor overtemperature
ow/return sensor differential alarm
ON
transitional
denitive
denitive
E077 main zone water thermostat ON transitional
E080
return line probe fault
return line probe overtemperature
outlet/return line probe differential alarm
ON
transitional
denitive
denitive
E090
ue gas probe fault
ue gas probe overtemperature
ashing 0,5 sec. ON/0,5 sec. OFF
transitional
denitive
E091 clean primary heat exchanger
ashing 0,5 sec. ON/0,5 sec. OFF
transitional
E099 reset attempts exhausted, boiler blocked
It is referred to the last fault occurred
denitive,
not resettable
-- water pressure low check system
ashing 0,5 sec. ON/0,5 sec. OFF
transitional
-- water pressure high check system
ashing 0,5 sec. ON/0,5 sec. OFF
transitional
-- boiler board communication lost ON transitional
-- BUS 485 communication lost ON transitional
List of combustion faults
ERROR
CODE
RED LED GREEN LED FAULT DESCRIPTION OF ALARM TYPE
E021
ON
ion alarm
These are temporary alarms that if they occur 6 times in an hour they become denitive; the E097 alarm is displayed and
is followed by post-purging for 45 seconds at the fan's maximum speed.
It is not possible to release the alarm before the end of the post-purging unless the boiler's power supply is switched off.
E022
ON
ion alarm
E023 ON ion alarm
E024 ON ion alarm
E067 ON ion alarm
E088 ON ion alarm
E097 ON ion alarm