8.Troubleshooting
8. 1 Error code display on LED wire controller
Inlet water
temperature sensor
failure T1-TH6
1. The sensor in open or short circuit
2. The wiring of sensor is loose
1. Check or change the sensor
2.Re-fix the wiring of the sensors
Outlet water
temperature sensor
failure T2-TH5
1. The sensor in open or short circuit
2. The wiring of sensor is loose
1. Check or change the sensor
2.Re-fix the wiring of the sensors
Heating piping
sensor failure
T3-TH2
1. The sensor in open or short circuit
2. The wiring of sensor is loose
1. Check or change the sensor
2.Re-fix the wiring of the sensors
1. The sensor in open or short circuit
2. The wiring of sensor is loose
1. Check or change the sensor
2.Re-fix the wiring of the sensors
Ambient
temperature sensor
failure T5-TH1
1. The sensor in open or short circuit
2. The wiring of sensor is loose
1. Check or change the sensor
2.Re-fix the wiring of the sensors
Dischargepiping
sensor failure
T6-TH3
1. The sensor in open or short circuit
2. The wiring of sensor is loose
1. Check or change the sensor
2.Re-fix the wiring of the sensors
Antifreeze
protection in Winter
Ambient temperature or water inlet
temperature is too low
Low ambient
temperature
protection
1.Beyond the scope of using
environment
2. Sensor abnormality
1.
Stop using, beyond the scope
of using
2.Change the sensor
Piping temperature
too high protection
under cooling mode
T3-TH2
1.
Ambient temperature is too high
or the water temperature is too high
in cooling mode
2. Refrigeration system is abnormal
1. Check the scope of using
2. Check refrigeration system
T2-TH5 water temp.
Too low protection
under cooling mode
1. Low water flow
2. T2-TH5 temperature sensor
abnormal
1.
Check filtration pump and
waterway system
2. Change T2-TH5 temperature
sensor
1. Ambient temperature is too high
2. Water temperature is too high
3.
Water flow is too low
Fan motor speed is abnormal or fan
motor has damaged
1. Check the water flow or
filtration pump
2. Check the fan motor
3. Check and repair the piping
system