Be42 OEM's Manual V5.0.XX - December - 2010 page 13
Table 7.02A - GENERATOR PARAMETERS Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
Parameter Code & Description
Under voltage (AUTO & TEST mode)
Under Hz (AUTO & TEST mode)
Over current shut down delay
(°) Mode1: The engine shuts down after a cooling down time ([P.24]). (°) Mode2: The engine shuts down without a cooling down time.
(°) Mode3: The Be42 provides a warning if the parameters rise above the setting for the specified timing.
Table 7.02B - GENERATOR PARAMETERS Note: [ oFF ] = disabled, [ on ] = enabled
Parameter Code & Description
Alternator failure options. The alarm [E04] energizes if the
voltage (or the frequency) is lower than the setting of P.9 (or
P11) for more than 150 seconds.
Alternator number of Poles. Options [2] or [4] allow you to
display the engine speed.
Generator Contactor Control. The option [off] inhibits Load
transfer to the generator in TEST mode (or remote TEST)
when MAINS is present.