Be42 OEM's Manual V5.0.XX - December - 2010 page 15
15
Table 7.04 - ALARM OPTIONS Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
Parameter Code & Description
Default
Min
Max
Options
P.33
Alarm bypass (for oil, temperature, auxiliary1-2-
3-4 alarms)
[ 5" ]
2secs
90secs
-
P.34
Fail to stop alarm control (oFF = inhibited,
on = enabled)
[oFF]
-
-
[oFF]/ [on]
P.35
Emergency contact type (Input #36). It
generates the alarm [Er.08]
[n.c.]
-
-
[n.o. / n.c.]
P.36
No fuel bypass timeout (it starts to count when
you activate the Low Fuel Input, terminal #33)
[ 5' ]
15secs
99mins
[oFF]
P.37
Low fuel % limit
[oFF]
1%
99%
[oFF]
P.38
High fuel % limit
[oFF]
1%
99%
[oFF]
P.39
Engine Temperature Switch type (input # 34)
[n.o.]
-
-
[n.o. / n.c.]
Table 7.05 - MISCELLANEOUS Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
Parameter Code & Description
Default
Min
Max
Options
P.40
EJP time
[ 5" ]
1 sec
99 mins
-
P.41
Periodic Test interval (see 16.10)
[oFF]
2 hours
9999h
[oFF]
P.42
Periodic Test duration (see 16.10)
[ 5' ]
1 min
99 mins
-
P.43
Test timeout ([OFF]= no timeout). It
limits the running time in case of
TEST initiated by a MODBUS
command.
[ 5' ]
1 min
99 mins
[oFF]
P.44
Maintenance SERVICE 1
(for the use, see section 16.40)
[oFF]
1h
9999h
[oFF]
P.45/46
Maintenance SERVICE 2 /3
(for the use, see section 16.40)
[oFF]
1h
9999h
[oFF]
P.47
Rental Contract Setting (see section
16.40)
[oFF]
1h
9999h
[oFF]
P.48
NFPA - 110 Level 1&2
[on]
-
-
[on]/[oFF]
P.49
RS485 Node Address
[ 1 ]
1
127
-
P.50
Horn timeout (see section 8.0)
[ 5" ]
5secs
15mins
[oFF]
P.51
Hour Counter set (over 9999, a dot
will appear to indicate a value
multiplied by10. Example 3250. will
indicate 32500 hours. In this case the
resolution is 10 hours).
[ 0 ]
0h
50.000
[oFF]