Operation of the flame amplifier
6-3
6.5 Operation settings
Prior to the initial operation, check the setting of the
switch-ON times and adjust, if and when necessary. DIP
switches S2 to S5 are accessible on the upper side of the
device. For this purpose pull the flame amplifier out of the
19" rack.
1 2
3 4 5 6
OFF
1 2
3 4 5 6
OFF
1 2
3 4 5 6
OFF
1 2
3 4 5 6
OFF
1 2 3
4
5
6
OFF
1
2
3
4 5 6
OFF
1 2
3 4 5 6
OFF
1
2
3
4
5
6
OFF
1
2
3
4 5 6
OFF
1
2
3
4 5 6
OFF
1
2
3
4 5 6
OFF
1 2
3 4 5 6
OFF
1
2
3
4
5
6
OFF
1
2
3
4 5 6
OFF
1
2
3
4 5 6
OFF
1 2
3 4 5 6
OFF
1 2
3 4 5 6
OFF
1
2
3
4
5 6
OFF
1
2
3
4
5 6
OFF
1
2
3
4
5
6
OFF
1
2
3
4
5
6
OFF
1
2
3
4
5
6
OFF
1
2
3
4
5
6
OFF
S5
S4
S3
S2
S1
1s
2s
3s
4s
5s
6s
A
B
C
25% 27% 30% 37% 50% 75%
S2 / S3
(RF)
S4 / S5
(RM)
S1
(2
0
- 2
5
)
F102
F101
X4
X5
X6
T
S1 switch-ON threshold
S2 switch-OFF time RF2
S3 switch-OFF time RF1
S4 switch-OFF time RM2
S5 switch-OFF time RM1
X4 switchover 0 to 4 ... 20 mA
X5 switchover – switch-ON delay
X6 switchover 0 to 4 ... 20 mA
F101 fuse - voltage supply
F102 fuse - relay contact
T Impulse dividing ratio 1:1 , 1:2 , 1:4