Name (number), function Adjustable value range Description
Default value
Tank dimensions (P41…P45), for
volume measurement
0…999 999 Typical dimensions in units of length
for the tank type set in parameter
P40 for volume calculation.
SAP–300: no adjustment available
0
Specific gravity (P32), for weight
measurement
0.01…100
If the device is set to weight
measurement, the specific gravity of
the material (medium) stored in the
tank must be entered here for weight
calculation. The value to be set is the
ratio (without unit) to the density of
the water.
SAP–300: no adjustment available
Threshold offset (P34), interference
sensitivity setting
-4095…+4095 Modifies the acceptance threshold
set on the echo chart. It can be
used it to increase (positive value)
or decrease (negative value) the
device’s ability to suppress the
interference signal relative to the
default setting. When set to 0,
there is no change from the original
setting.
SAP–300: MAIN MENU / MEAS.
OPTIMIZATION / THRESHOLD
OFFSET
0
Gross tank volume (P47)
0…999 999 Adjusts the transmitted quantity
by distance. If the value measured
by the device differs from the value
under real conditions, this multiplier
can be used to adjust the result.
The output value is multiplied by
the number set here. The default
multiplier is 1, which does not
change the output.
SAP–300: no adjustment available
0