EasyManuals Logo
Home>Bitzer>Control Unit>CM-SW-01

Bitzer CM-SW-01 User Manual

Bitzer CM-SW-01
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
14 SG-150-1
5.3 Required signals to start the compressor
Min. signals required to start the compressor via the CM-SW-01
5.3.1 Digital and analogue signals
Serial Control Source = 0 (None)
Start command
CN2:Relay C
Setpoint
CN13:Cap. Input
Compressor
State
Stopped
Off
Stopped
On
0 100%
Running
Note: Please observe max number of starts per hour
5.3.2 Serial control (Modbus)
Serial Control Source = 1 (Modbus)
Start command
Control Word
Setpoint
Serial Setpoint
Compressor
state
Stopped
Off
Stopped
On
±100 %
Running
Note: Please observe max number of starts per hour
Control commands can be given to the CM-SW-01 via the Serial Control Word. The bit definitions are shown
in the table below.
The protocol used is Modbus (RTU). Modbus register definitions are listed in section 10.3
Parameters.
5.4 Control Word bit definitions
Bit
Function
Description
0-2
Reserved
Must be set to 1
3
Operation enable
Enable operation (0=off, 1 = enabled)
4
Reserved
Must be set to 1
5
Reserved
Must be set to 1
6
Start
Start command is active when bit = 1
7
Reset
Reset alarm command is active when bit is set from 0 to 1.
Positive edge triggered.
8-9
Reserved
10
Data valid
Instruct controller to accept control word. Otherwise all other bits
are ignored.
The resulting control word will always have this set.
Please see section 10.3.1 Control application
11-15
Reserved
The data valid bit must be set to update the serial control word and the serial setpoint.
The Control Word is the active control word.
Use the Serial Control Word for configuration of the CM-SW-01.
5.4.1 Data valid bit
When the data valid bit is set to “1” setpoint and commands are accepted from the serial control interface.
When the data valid bit is set to “0” all other bits in the control word and the setpoint are ignored. This
means that if the start command was active just before the data valid bit is set to “0” the command remains
active until the data valid bit is set to “1” and the start bit is set to “0”.
Please note that the Serial Control Source must be 1 (Modbus).

Table of Contents

Other manuals for Bitzer CM-SW-01

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bitzer CM-SW-01 and is the answer not in the manual?

Bitzer CM-SW-01 Specifications

General IconGeneral
BrandBitzer
ModelCM-SW-01
CategoryControl Unit
LanguageEnglish

Related product manuals