KT-200-2 27
y Enclosure class
- terminal box of control IP65
- terminal box of compressor IP65
- frequency inverter IP54
- High pressure switch IP54
y Minimum requirements for the use of
residual current circuit breakers
- Use a residual current circuit
breaker, type B (inverter-resistant),
sensitive to all current types, with a
nominal residual current of 100 mA
if the discharge current is to be
protected.
- Such a circuit breaker is not
suitable for personal protection.
- Additional appropriate measures
have to be taken for personal
protection!
y Compliance with the EU directive
2004/108/EC (electromagnetic
compatibility, EMC), class B1
y 保護等級
- 制御の端子ボックス IP65
- コンプレッサーの端子ボックス
IP65
- 周波数インバーター IP54
- 高圧スイッチ IP54
y 残留電流ブレーカーを使用するため
の最低要求事項
- すべての電流タイプに反応する残留
電流ブレーカー、タイプB(耐イン
バーター)の使用、公称残留電流
100 mA(放電電流を保護する必要が
ある場合)。
- この種のブレーカーは人員の保護に
は適しません。
- 人員を保護するためには、他に適切
な処置を講じる必要があります。
y EU 指令 2004/108/EC(電磁適合性、
EMC、クラス B1 の順守