42 KT-200-2
y Mount the front grating of the
weather protective housing.
y Mount main fuse and switch on main
switch.
y Switch off the speed regulator in the
control:
Set NO or NEIN in menu 4.3.3 (FAN
CTRL).
y Switch on the control in menu 3.2
(M
ODE or MODUS): Switch to ON or
EIN.
y Close the control panel cover.
The control now activates or deactivates
one or both condenser fans depending
on the current load of the condensing unit.
6.5 Resetting factory settings
A
ll parameters are reset to factory
settings. Therefore, we recommend to
note down before the most important
basic settings (at least menu 4.1 BASIC
SETTING
or GRUND-EINSTEL).
y Set the control to O
FF or AUS in menu
3.2 (MODE or MODUS).
y Select Y
ES or JA in menu 4.3.4
(RESET or RÜCKSETZEN).
The English menu 1 (S
ET -10 R404A) is
displayed. All settings are as in the
menu structure in chapter 7 on the last
double page. Any differing parameters
must be entered again.
y 耐候性ハウジングのフロントグリル
を取り付けます。
y メインヒューズを取り付けて、メ
インスイッチをオンにします。
y 制御中の速度制御をオフにします。
メニュー4.3.3FAN CTRL)で NO また
N
EIN を設定します。
y メニュー3.2M
ODE または MODUS
で制御をオンにします。O
N または EIN
に切り換えます。
y コントロールパネルカバーを閉じ
ます。
この後、制御はコンデンシングユニット
の現在の負荷に応じて、コンデンサー
ファンの1つまたは両方をオンまたはオ
フにします。
6.5 工場設定へのリセット
すべてのパラメーターは工場設定にリ
セットすることができます。そのため、
最も重要な基本設定(少なくともメニュー
4.1 B
ASIC SETTINGまたはGRUND-EINSTEL)は
書き留めておくことを推奨します
y メニュー3.2M
ODE または MODUS
で制御を O
FF または AUS 設定し
ます。
y メニュー4.3.4RESET または
RÜCKSETZEN)で YES また JA を選択
します。
英語メニュー1S
ET -10 R404Aが表示
されます。すべての設定は、7章の最後
の見開きページのメニュー構造に記載さ
れています。これと異なるパラメーター
は再入力してください。