Orion ISS
www.bolid.com 42
Partition Armed
ARM 7 U 80
The
partition #7 has just been armed in response to
presenting user authenticator #80
Partition Disarmed
DARM 7 U 11
The
partition #7 has just been disarmed in response
to presenting user authenticator #11
Loop Armed
ARM 7 018/003
The alarm loop #3 connected to the device #18 and
included into the partition #7 has just been armed
Loop Disarmed
DARM 7 018/003
The alarm loop #3 connected to the device #18 and
included into the partition #7 has just been disarmed
Arming Failed
FARM 7 018/003
Arming the loop #3 connected to the device #18 and
included to the partition #7 has failed
Zone
Disconnected
ZTD 2 007/001
An addressable device which belongs to the partition
#2 has been disconnected from the polling loop of the
S2000-KDL with the network
address 7; the number of
the device in the polling loop is 1
Loop Open Failure
LTO 14 001/003
An open circuit failure
has been detected within the
alarm loop #3 which belongs to the device #1 and is
included into the partition #14
Loop Short Failure
LTS 14 001/003
A short circuit failure
has been detected within the
a
larm loop #3 which belongs to the device #1 and is
included into the partition #14
Fire Signal
FS 14 001/003
A fire detector response has been received via the
alarm loop #3 connected to the device #1 and in-
cluded into the partition #14
Intrusion
Alarm
IA 7 018/003
The alarm loop #3 connected to the device #18 and
included into the partition #7 has just been broken
Silent Alarm
SA 1 018/002
The alarm loop #2 connected to the device #18 and
included into the partition #1 has just been broken
Fire Pre-Alarm
FPA 14 001/003
The alarm loop #3 of the device #1 included into the
partition #14 has responded with the Fire Prealarm
status which means that fire can happen within the
protected area
Fire Alarm
FA 14 001/003
The alarm loop #3 of the device #1 included into the
partition #14 has responded with the Fire Alarm status
Loop Tamper
Alarm
TA 7 001/004
Opening (tampering) the enclosure of the detector in-
cluded into the intrusion alarm loop #4 of the device
#1 included into the partition #7
Loop Tamper
Restored
TR 7 001/004
Closing the enclosure of the detector included into the
intrusion alarm loop #4 of the device #1 included into
the partition #7