173_58300000002379_ara_en_j.doc – 29.04.14 Seite 34 von 41
No or too low
cooling power.
Compressor runs
Change of compressor only in case of a
leakage on the low pressure side
Check back pressure at the
0,6 bar in the steady state
Change of compressor only in case of a
missing back pressure (no pressure drop
during operation can be noticed)
In case of a low back pressure (<0,3 bar):
Lack of refrigerant or cycle blocked.
The compressor contacts the
housing
Check the compressor mounting
refrigeration cycle parts.
Dampen the tubes (abolish vibrations at the
when starting or running out.
Check the compressor mounting -
In case of abnormal noise – change of