34 en | Specifications
2016.07 | 04 | F.01U.291.483 UL Installation Guide Bosch Security Systens, Inc.
Terminal
No
Terminal
Description
Requirements
34 SDI2 DATA
BUS B
22 AWG min (up to 14 AWG max)
35 SDI2 DATA
BUS A
22 AWG min (up to 14 AWG max)
36 SDI2 POWER Terminal accommodates 14 to 22 AWG, use appropriate wire size based on peripheral
device current.
*D9412GV4 only. Terminals 25 and 26 are NOT USED on the D7412GV4 Control Panel.
5.3 Compatibilities
Notice!
Where the fire alarm transmitter is sharing on-premise communications equipment, the
shared equipment must be UL Listed (ITE or fire protective signaling).
Compatible Accessories
1
Model Title UL 864 UL
985
Intrusion cUL
Intrusion
B208 Octo-input Module X X X X
B308 Octo-output Module X X X X
B426/B420 Conettix Ethernet Communication Module X X X X
B440
5
Plug-in Cellular Communicator (using 3G) X X X
B441
5
Plug-in Cellular Communicator (using CDMA) X X X
B442 Plug-in Cellular Communicator
1, 6
(using GPRS) X X X X
B443 Plug-in Cellular Communicator
1, 6
(using HSPA+) X X X X
B450 Plug-in Communicator Interface X X X X
B520 Auxiliary Power Supply Module X X X X
B810
3
RADION receiver SD X X
B820
2
Inovonics Interface Module X X
B915 Basic Keypad X X X
B920 Two-line Alphanumeric Keypad X X X
B921C Two-line Capacitive Keypad X X X
B930 ATM Style Alphanumeric Keypad X X X
B942/B942W Touch Screen Keypad X X X
D113 Battery Lead Supervision Module X X X X
D122/D122L Dual Battery Harness X X X
D125B Powered Loop Interface Module X X X X