Fire Alarm Systems | F220 Photoelectric Smoke Detectors
F220 Photoelectric Smoke Detectors
www.boschsecurity.com
u Two-wire or four-wire bases
u 30 ft (9 m) maximum spacing between detectors
u Optional CO-sensor, heat-sensor enhanced
detection chamber
u Clean chamber without removal or disassembly
u CleanMe signaling capability
The F220 Photoelectric Smoke Detectors are UL
Listed, open-area photoelectric smoke detectors. Use
them with commercial fire protective signaling
systems and household fire warning systems (see
NFPA 72, the National Fire Alarm Code). These smoke
detectors scatter light using a pulsed infrared source
operating with a gated, high-speed, photodiode
infrared sensor. The symmetry of the optical chamber
allows 360° uniform smoke entry, but minimizes
external light entry. The detectors use low current
electronic circuitry, so they can connect to 12 VDC
nominal or 24 VDC nominal power source circuits.
Functions
Compatible Bases
Configure the detectors into two-wire or four-wire
versions by selecting the appropriate mounting base.
These detectors are compatible with any of the
F220‑B6 bases:
F220-B6 12/24 VDC Two‑wire Mounting Base
F220-B6R Standard 12/24 VDC Four‑wire Mounting
Base
F220-B6RS 24 VDC Four‑wire Mounting Base with
Sounder
F220-B6C 12/24 VDC Four‑wire Mounting Base with
Auxiliary Relay
F220-B6E 12/24 VDC Four‑wire Power Supervision
Mounting Base
F220-B6PM 24 VDC Four‑wire Addressable Master
Base
F220-B6PS 12/24 VDC Four‑wire Addressable Base
Monitoring the Detection Chamber
These detectors have several features that work
together to maximize the performance of the optical
chamber:
Compensation: The detector monitors the chamber
for the effects of dust build-up within the chamber
and automatically compensates for these effects. If
the chamber becomes contaminated beyond its
ability to compensate, the green LED flashes every
4 sec to indicate trouble.
Chamber Check Self-diagnostics: The detector
automatically indicates visually if the calibration is out
of the factory-listed range. This meets NFPA
guidelines for sensitivity testing, because you can
visually inspect the detector and check the flash rate
of the LED. If the calibration is out of range, the green
LED on the detector flashes once every 4 sec. This
indicates that the detector must be cleaned following
the instructions provided with the detector.

Other manuals for Bosch F220 Series

Question and Answer IconNeed help?

Do you have a question about the Bosch F220 Series and is the answer not in the manual?

Bosch F220 Series Specifications

General IconGeneral
BrandBosch
ModelF220 Series
CategorySmoke Alarm
LanguageEnglish

Summary

Functions

Compatible Bases

Lists the F220-B6 bases compatible with the detectors for configuring two-wire or four-wire versions.

Monitoring the Detection Chamber

Details features like Compensation and Self-diagnostics to maximize optical chamber performance and indicate issues.

Detector Features and Enhancements

Heat and Carbon Monoxide Enhancements

Describes optional heat and CO sensors that reduce false alarms and improve smoke detection sensitivity.

Dual-color LED and Test Functions

Explains the LED indicator states for normal operation, alarm, and trouble, plus magnet-based testing.

Tamper Detection

Covers the positive power line tamper detection and mechanical tamper lock features for base security.

Certifications and Installation

Certifications and Approvals

Lists regions and corresponding certifications, including UL, FM, CSFM, NYC-MEA, MSFM, and HKFSD.

Installation and Configuration Notes

Provides guidance on compatible control panels, two-wire and four-wire system integration, and base mounting.

Technical Specifications and Ordering

Technical Specifications

Details environmental considerations, mechanical properties, power requirements, and voltage ranges for bases.

Ordering Information

Lists available detector heads (PTHC, PTH, P) and accessories like power supervision modules and mounting bases.

Related product manuals