Aspiration smoke detectors LSN improved Technical data | en 27
Bosch Sicherheitssysteme GmbH Quick installation guide 2020.04 | 5 | F.01U.029.274
– DM‑TT‑50(80) Detector Module 0.5%/m (0.8%/m) *
– DM‑TT‑10(25) Detector Module 0.1%/m (0.25%/m) *
– DM‑TT‑01(05) Detector Module 0.015%/m (0.05%/m) *
Service life of the fan (12V) 43,000 hrs at 24°C
* The sensitivity value is based on measurements with standard test fires (old value in
brackets).
SL variants
Electrical
LSN power supply 15VDC to 33VDC
Auxiliary power supply 14VDC to 30VDC
LSN current consumption 6.25mA
Current consumption from auxiliary power supply
(at24V)
FAS-420
-TP1-SL -TP2-SL -TT1-SL -TT2-SL
– Starting current, fan voltage 6.5V 190mA 250mA 190mA 250mA
– Starting current, fan voltage 6.9V 190mA 250mA 190mA 250mA
– Starting current, fan voltage 9V 190mA 250mA 190mA 250mA
– On standby, fan voltage 6.5V 130mA 170mA 130mA 170mA
– On standby, fan voltage 6.9V 140mA 180mA 140mA 180mA
– On standby, fan voltage 9V 170mA 210mA 170mA 210mA
– On alarm, fan voltage 6.5V 150mA 180mA 150mA 180mA
– On alarm, fan voltage 6.9V 160mA 200mA 160mA 200mA
– On alarm, fan voltage 9V 190mA 230mA 190mA 230mA
Mechanics
Displays on the device FAS‑420‑TP1/FAS‑420‑TP2
– Power Green LED
– Fault yellow LED
– Alarm 1 red LED/2 red LEDs
Displays on the device FAS‑420‑TT1/FAS‑420‑TT2
– Power Green LED
– Fault Yellow LEDs
– Level display 1 x / 2 x smoke level display, each
with 10segments (1-10)
– Alarm 1 x 3 / 2 x 3 red LEDs for info alarm,
internal-alarm and main alarm
Conical duct connections for Ø25mm