FCP-500 Conventional Flush-mount Smoke Detectors | 3
Parts Included
The FCP Series products are available individually or in
kits. The kits contain:
FCP-500-K
Quant. Component
1 FCP-500 Four-wire Detector Head (white)
1 FAA-500-BB-UL Flush-mount Back Box
1 FCA-500 Four-wire Detector Base
1 FAA-500-TR-W Trim Ring (white)
FCP-500-PK
Quant. Component
1 FCP-500-P Four-wire Detector Head (transparent)
1 FAA-500-BB-UL Flush-mount Back Box
1 FCA-500 Four-wire Detector Base
1 FAA-500-TR-P Trim Ring (transparent)
16 Color insert rings
FCP-500-EK
Quant. Component
1 FCP-500 Four-wire Detector Head (white)
1 FAA-500-BB-UL Flush-mount Back Box
1 FCA-500-E Four-wire EOL Detector Base
1 FAA-500-TR-W Trim Ring (white)
FCP-500-EPK
Quant. Component
1 FCP-500-P Four-wire Detector Head (transparent)
1 FAA-500-BB-UL Flush-mount Back Box
1 FCA-500-E Four-wire EOL Detector Base
1 FAA-500-TR-P Trim Ring (transparent)
16 Color insert rings
FCP-500-CK
Quant. Component
1 FCP-500-C Four-wire Detector Head with CO Sensor (white)
1 FAA-500-BB-UL Flush-mount Back Box
1 FCA-500 Four-wire Detector Base
1 FAA-500-TR-W Trim Ring (white)
FCP-500-CPK
Quant. Component
1 FCP-500-C-P Four-wire Detector Head with CO Sensor (transparent)
1 FAA-500-BB-UL Flush-mount Back Box
1 FCA-500 Four-wire Detector Base
1 FAA-500-TR-P Trim Ring (transparent)
16 Color insert rings
FCP-500-CEK
Quant. Component
1 FCP-500-C Four-wire Detector Head with CO Sensor (white)
1 FAA-500-BB-UL Flush-mount Back Box
1 FCA-500-E Four-wire EOL Detector Base
1 FAA-500-TR-W Trim Ring (white)
FCP-500-CEPK
Quant. Component
1 FCP-500-C-P Four-wire Detector Head with CO Sensor (transparent)
1 FAA-500-BB-UL Flush-mount Back Box
1 FCA-500-E Four-wire EOL Detector Base
1 FAA-500-TR-P Trim Ring (transparent)
16 Color insert rings
Technical Specifications
Detection Principle
FCP-500(-P): Scattered light measurement
FCP-500-C(-P): Combination of scattered light measurement and CO
measurement
Drift Compensation
all FCP-500 detectors: Drift compensation for smoke sensor baseline
(optical sensors)
in addition,
for FCP-500-C(-P):
Drift compensation for CO sensor
Environmental Considerations
Air Speed 300 ft
3
/min (8.5 m
3
/min) maximum
Humidity 95% (non-condensing)
Interference Immunity: According to UL 268
Operating Temperature +32 °F to +100 °F
Protection Category: FAP-500(-C): IP 53
FAP-500(-C)-P: IP 33
Mechanical Properties
Color:
Detector Housing: Signal white, RAL 9003
Detector Front Plate: FCP-500(-C): signal white
FCP-500(-C)-P: transparent (color inserts)
Dimensions (diameter x D)
Detector: 4.5 in. x 2.2 in. (11.4 cm x 5.6 cm)
Detector with Trim Ring: 5.9 in. x 2.2 in. (15 cm x 5.6 cm)
Detector with Trim Ring and
Base:
5.9 in. x 2.75 in. (15 cm x 7 cm)
Material: Polycarbonate
Mounting Considerations
Area Monitored: Refer to NFPA 72 Guideline
Mounting Height: Maximum: Refer to NFPA 72 Guidelines
Minimum: 8.8 ft (2.7 m)
False Ceiling
Clearance (minimum): 6 in. (15.2 cm) with tolerances of -0.0625 in.
(1.6 mm) and +0.1875 in. (4.8 mm)
Mounting Hole: 5.0625 in. (12.9 cm)
Thickness (maximum): 1.25 in. (3.2 cm)
Outputs
Alarm
Output: Alarm output through normally-open (NO) relay in FCA-
500 base. An alarm resistance of 0 or 680 in series
to the relay can be adjusted.
Relay Rating: 1 A at 30 VDC
Reset Time The detector resets if power is interrupted for at least
2 sec.
Display
Two-color LED: Red = alarm, green = test mode
www.boschsecurity.com