Greentherm T9800 SE(C) 160/199 Application Manual
06.2017 | Bosch Thermotechnology Corp.Data subject to change
3.3 Tankless water heater speci cations
Description Unit T9800 SE 160 T9800 SE 199
Performance
Maximum gas input BTU/hr (kW) 160,000 (46.64) 199,000 (58.3)
Minimum input BTU/hr (kW) 9,000 (2.6) 9,000 (2.6)
Maximum output BTU/hr (kW) 157,608 (46.2) 197,010 (57.7)
Thermal effi ciency (Effi ciency in %) % > 99% > 99%
Maximum fl ow rate at a 35 °F (19.4 °C) rise¹ GPM (l/min) 9.0 (34) 11.2 (42.4)
Maximum fl ow rate at a 45 °F (25 °C) rise GPM (l/min) 7.0 (26.7) 8.7 (27.7.9)
Maximum fl ow rate at a 55 °F (30.6 °C) rise GPM (l/min) 5.8 (21.9) 7.2 (27.5)
Maximum fl ow rate at a 75 °F (41.7 °C) rise GPM (l/min) 4.2 (15.9) 5.2 (19.7)
Maximum fl ow rate at a 90 °F (50 °C) rise GPM (l/min) 3.5 (13.2) 4.4 (16.6)
Temperature Control
Selection range °F ( °C)
100 - 120³ (38 - 49)
100 - 120³) (38 - 49)
Default temperature⁵ °F ( °C) 120 (49) 120 (49)
Temperature stability
°F ( °C) ± 2 (± 1) ± 2 (± 1)
Gas Requirement
Gas connection inches ¾ ¾
Inlet gas pressure range NG / LP Inch W.C. 3.5” - 10.5” / 8” - 13” 3.5" - 10.5" / 8" - 13"
Water
Top hot water connection NPT inches ¾" ¾"
Top cold water connection NPT inches ¾" ¾"
Minimum water fl ow
GPM (l/min) 0.45 (1.7) 0.45 (1.7)
Maximum water pressure PSI (bar) 150 (10.3) 150 (10.3)
Minimum recommended water pressure PSI (bar) 18 (1.2) 18 (1.2)
Minimum well pressure PSI 30 30
Water valve material Polymer (PPS) (Polypropylene Polymer (PPS) (Polypropylene
Combustion
CO level ppm ≤ 250 (measured) ≤ 250 (measured)
CO2 level (set from factory) % see installation manual see installation manual
Weight
Net weight pounds (kg) 73.2 (33.20) 77.5 (35.15)
Gross weight pounds (kg) 79.37 (36.0) 83.67 (37.95)
Electrical
Voltage V AC 120 120
Frequency Hz 60 60
Amperage (Idle) mA 40 40
Amperage (operation) A ≤ 2.7 ≤ 2.7
Water protection IP X4D X4D
Venting
Venting category IV IV
Approved vent or combustion air pipe material - United States PP fl exible/concentric/rigid, PVC sched. 40, PVC-DWV, CPVC sched. 40, ABS-DWV sched. 40
Approved vent or combustion air pipe material - Canada CSA or ULC certifi ed only (ULCS636)
Table 3
¹ These fl ow are based upon setting the unit to higher temperatures and then mixing down using cold water after
the unit, to reach these fl ow rates.
²
Input rating is based on sea level operation and need not be changed for operation up to 2000 ft (610 m)
elevation. For
operation at elevations above 2000 ft (610 m), input rating is automatically reduced at the rate
of 4 percent for each 1000 ft (305 m) above sea level.
³ When converted to LPG the minimum input is 17 000 BTU/hr (5 kW).
⁴ With constant fl ow.
⁵ Can be reprogrammed to achieve up to 140 °F (60 °C).
⁶ Requirements: Steady fl ows, single unit installations, up to 140 °F (60 °C).
⁷ To measure Gas Pressure, see installation manual - Measuring Gas Pressure, chapter 4.13, page 36.
⁸ Refers to activation point. Deactivation point value is 0.35GPM (1.3 l/min).
 Protection against water drops.