Problem solving
Greentherm T9900 SE/i – 6 720 813 635 (2019/03)
68
AA Condensing unit flue gases temperature [16]
above 392 °F (200 °C) and/or flue gases
temperature [15] above 145 °F (63 °C) at the
exhaust sensor [15]. Appliance regulates power to
protect against overheating.
Descale appliance ( section 7.3).
1)
BB Fan calibration triggered due to missed ignitions. Check gas inlet pressure ( section 4.13).
1)
Perform gas and air tuning ( section 8.12).
1)
BC Successive fan calibration with similar learned
values.
Check gas inlet pressure ( section 4.13).
1)
Perform gas and air tuning ( section 8.12).
1)
C1
C2
Flue blockage detected during startup due to
insufficient combustion air.
Reset error (touch and hold on/off button for 3
seconds).
If the problem persists:
Check air intake and exhaust pipes and terminals for
obstructions and reset the error.
Check if flue length is according to specification
(section 4.6) and reset the error.
Perform gas and air tuning ( section 8.12).
1)
C3 Flow sensor [14] does not detect water
recirculation.
Check pump and connections.
1)
Check recirculation circuit for any blockage.
C5 Bypass water valve [8] disconnected or damaged. Check bypass water valve wire connections.
1)
If the problem persists:
Replace the bypass water valve and/or wire
connections. After valve replacement, proceed with
bypass water valve calibration (section 6.7).
1)
C7 Fan [2] disconnected or damaged. Check fan wire connections.
Reset error (touch and hold on/off button for 3
seconds)
If the problem persists:
Replace the fan and/or wire connections.
1)
C8 Main water valve [22] disconnected or damaged. Check main water valve wire connections.
1)
Proceed with main water valve calibration.
If the problem persists:
Replace main water valve and/or wire connections.
After valve replacement, proceed with main water
valve calibration (section 6.7).
1)
C9 Barometric pressure sensor damaged. Reset error (touch and hold on/off button for 3
seconds).
If the problem persists:
Replace electronic control unit (ECU).
1)
CA Water flow above 9.2gpm. Disconnect the appliance and purge hydraulic circuit
to remove air.
1)
Install water flow restrictor.
1)
Check water pressure does not exceed 150psi
(section 3.2).
Display Description Solution