EasyManua.ls Logo

Bosch SSB800 SA - Appendix I - Venting Size Data

Bosch SSB800 SA
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SSB 6720866942 (2018/06) US
VENTING SIZE DATA | 57
Appendix I - Venting size data
SSB 800 SA
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 0,21 0,02 0,21 0,02
Flue temperature °F 167 147,2 104 89,6
Max. pressure at boiler exit in. wc 0,83 0,04 0,72 0,03
SSB 1000 SA
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 0,26 0,02 0,26 0,02
Flue temperature °F 176 152,6 104 91,4
Max. pressure at boiler exit in. wc 0,91 0,05 0,83 0,03
SSB 1000 TL
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 0,26 0,02 0,53 0,02
Flue temperature °F 176 152,6 104 91,4
Max. pressure at boiler exit in. wc 0,96 0,05 0,86 0,03
SSB 1000 TL2
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 0,53 0,02 0,53 0,02
Flue temperature °F 176 152,6 104 91,4
Max. pressure at boiler exit in. wc 0,91 0,05 0,82 0,03
SSB 1000 TL3
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 0,79 0,02 0,79 0,02
Flue temperature °F 176 152,6 104 91,4
Max. pressure at boiler exit in. wc 0,79 0,05 0,71 0,03
SSB 1000 TL4
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 1,06 0,02 1,06 0,02
Flue temperature °F 176 152,6 104 91,4
Max. pressure at boiler exit in. wc 0,59 0,05 0,51 0,03

Table of Contents

Other manuals for Bosch SSB800 SA