70 | Fitting
UNIMAT6 720 807 794 (2013/04)
10.3.2 Installation room dimensions for the UNIMAT UT-L boilers with flue gas heat exchanger
Fig. 48 UNIMAT UT-L boiler installation room dimensions
Allow extra space for sound insulation measures.
Maintain the specified wall clearances to facilitate
installation, service and maintenance work.
H
A
1
L
1
L
2
A
2
6 720 642 347-61.1il
UNIMAT UT-L boiler Installation room dimensions
1)
1) The values given are a guide. They may differ subject to the individual system.
Boiler size Length
2)
2) Length L
1
relative to a flue gas heat exchanger with a tube bundle element; with a flue gas heat exchanger with two tube bundle
elements, the length increases by 300 mm.
Height Side clearance
3)
3) Subject to the burner; the values given are a guide. The burner door can pivot either to the right or left.
L
1
L
2
H A
1
A
2
[mm] [mm] [mm] [mm] [mm]
UT-L 4 UT-L 2 2700 500 3500 700 1300
UT-L 10 UT-L 6 2950 500 3800 700 1300
UT-L 14 UT-L 8 3200 500 4100 800 1300
UT-L 18 UT-L 12 3700 500 4100 900 1300
UT-L 24 UT-L 16 3700 500 4400 900 1500
UT-L 28 UT-L 20 4050 500 4400 950 1500
UT-L 30 UT-L 22 4450 500 4600 950 1550
UT-L 34 UT-L 26 4600 500 5100 950 1650
UT-L 40 UT-L 32 5000 500 5600 950 1800
UT-L 42 UT-L 36 5200 500 On request 1000 1800
UT-L 46 UT-L 38 5450 500 On request 1000 On request
UT-L 50 UT-L 44 5900 500 On request 1000 On request
UT-L 54 UT-L 48 6200 500 On request 1000 On request
UT-L 58 UT-L 52 6950 500 On request 1000 On request
UT-L 60 UT-L 56 7400 500 On request 1050 On request
UT-L 64 UT-L 62 7850 500 On request 1050 On request
Table 32 UNIMAT UT-L boiler installation room dimensions (dimensions of the boiler foundation
Tab. 39, page 78)