51
ENGLISHAPPENDIX A ITALIANO
DFLT PAR. DESCRIPTION SET VALUES
0
P01
System type
0
2-pipes system
1
4-pipes system
2
Electric heater
3
Integrating
electric heater
0
P02
Heating/cooling
selection
0
Manual
1
Automatic
2
Remote
3
P03
Heating
regulation
1
Fan always ON
2
Valve always ON
3
Valves and fan
4
Fan always OFF
5
Valve always
OFF
3
P04
Cooling
regulation
1
Fan always ON
2
Valve always ON
3
Valves and fan
4
Fan always OFF
5
Valve always
OFF
0
P05
Fan output type
0
Proportional,
direct action
1
Proportional,
inverse action
2
3 speeds relays
2
P06
Heating output
type
0
Proportional,
direct action
1
Proportional,
inverse action
2
NC ON/OFF
valve
3
NO ON/OFF
valve
2
P07
Cooling output
type
0
Proportional,
direct action
1
Proportional,
inverse action
2
NC ON/OFF
valve
3
NO ON/OFF
valve
0
P08
Supply water
sensor input
0
Do not show
temperature
1
Show
temperature
2
Bi-metallic
contact
0
P09
De-stratication
0
Never
1
Cooling only
2
Heating only
3
Always
1
P10
On/Off state
at power up
1
Last
2
Always ON
3
Always OFF
0 P11
Room temperature
sensor
0
Internal
1
External
Table 1: Main conguration parameters (to set temperatures to Fahrenheit degrees see appendix A page 57).