11.2.4.12 Diagnostic value '13.PRPST' - Time since last Partial Stroke Test'
Indication on the display: • ###
• notSt
• Sdtst
• FdtSt
Purpose:
This diagnostics parameter shows the elapsed time in days since the
last Partial Stroke Test.
Status messages: • notSt - No Test: A Partial Stroke Test has not yet been executed.
• SdtSt - Stopped Test: The last Partial Stroke Test was interrupted.
• FdtSt - Failed Test: The last Partial Stroke Test failed
11.2.4.13 Diagnostic value '13.PRPST' - Time since last Partial Stroke Test' with option -Z P02
Indication on the display: • ###
• notSt
• norEF
• Sdtst
• FdtSt
Purpose:
This diagnostics parameter shows the elapsed time in days since the
last Partial Stroke Test.
Status messages: • notSt - No Test: A Partial Stroke Test has not yet been executed.
• norEF: A reference PST has not yet been executed.
• SdtSt - Stopped Test: The last Partial Stroke Test was interrupted.
• FdtSt - Failed Test: The last Partial Stroke Test failed
11.2.4.14 Diagnostic value '14.NXPST - Time until next Partial Stroke Test'
Requirement: • The Partial Stroke Test is activated in 'Conguration' mode.
• The test interval is set in the 'A8.INTRV' parameter.
Indication on the display: • OFF
• ###
Purpose: This diagnostics parameter shows the time in days until the next
Partial Stroke Test. If one of the above-mentioned conditions is not
met, 'OFF' is shown on the display.
Diagnostics and troubleshooting
11.2 Diagnostics
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 10/2020, A5E00074631-AF 223