ComAp, spol s.r.o.
Kundratka 2359/17
180 00, Praha 8
Czech Republic
InteliNano-NT MRS, SW version 1.1, ©ComAp – February 2012 1
InteliNano-NT-MRS-1.1-Fast User Guide.pdf
G
ECU
DIESEL / GASOLINE ENGINE GENERATOR
LOAD
Fuel Solenoid
Battery
Sarter
Fuel Level Analog
Coolant Temperature Analog
Oil Pressure Analog
D+
-
+
Alarm
Ready To Load
Fuel Solenoid
Starter
COM
Remote Start And Load
Emergency Stop
CAN
L COM H
USB
Battery +
Battery -
D +
PC
L1
L2
L3
N
INTERFAZ CAN
MEDIDA DE TENSION
DE GENERADOR
T16 = Neutro
T17 = Fase 1
T18 = Fase 2
T19 = Fase 3
Interfaz USB
L
COM
H
TERMINALES DE ENTRADAS
T10 = COM para entradas analógicas
T11 = entrada binaria
T12 = entrada binaria
T13 = Entrada bin./anal. Bajo nivel de comb
T14 = Entrada bin./anal. Temperatura motor
T15 = Entrada bin./anal. Presion aceite
TERMINALES DE SALIDAS
T04 = salida binaria Arranque (6A
T05 = salida binaria - Solenoide comb (6A)
T06 = salida binaria (500 mA)
T07 = entrada/salida binaria (500mA)
ALIMENTACIÓN, D+
T01 = BAT -
T02 = D+
T03 = BAT +
InteliNano NT
MRS Guia rápida de usuario
Esquema típico
Accediendo al modo programación
Asegurese de que el motor está parado y en controlador en modo Manual (el LED verde sobre el botón Auto está apagado).
Si no ha configurado la pantalla inicial personalizada, mantenga presionado el botón Stop, pulse brevemente el botón y entonces pulse Auto.
Si ha creado su popia pantalla inicial, mantenga presionado el botón Stop y entonces pulse brevemente , aparecerá la pantalla personalizada, mantenga presionado
el botón Stop. Entonces pulse para cambiar a la pantalla por defecto, y por último presione Auto.
Para desplazarse por el menú utilice los botones y . Pulse Start para seleccionar o Stop para salir.
Basic settings (Parámetros básicos)
Input settings (Ajustes de entradas)
Engine parameters and protections (Parámetros y protecciones
de motor)
ECU setting (Ajustes ECU)
Generator protections (Protecciones de generador)
Info (Información)
Output settings (Ajuste de salidas)
Entradas y salidas
Salidas
código
Fuente de la salida
Asignación del terminal
O00
No Usado
T04 , T05, T06, T0
O01
Arranque
T04
O02
Solenoide combustible
T05
O03
Solenoide parada
T05
O04
Alarma
T04, T05, T06, T07
O07
Preparado para meter carga
T04, T05, T06, T07
O08
Prearranque
T04, T05, T06, T07
O09
Relé de Potencia ECU
T04, T05, T06, T07
Contacto NC – salida
Contacto NA - entrada
Contacto NA – salida
Contacto NC – entrada
User curves
I21
I23
I25
VDO Nivell %
VDO 5 Bar
VDO 40-120 °C
Datcon Nivel %
VDO 10 Bar
VDO 50-150 °C
Datcon 5 Bar
Datcon High °C
Datcon 7 Bar
Datcon Low °C
Datcon 10 Bar
No seleccionado
No seleccionado
No seleccionado
Input
code
Input source
Type
Terminal assignment
I00
Not Used
binary
T07, T11, T12, T13, T14, T15
I01
Emergency Stop
binary
T07, T11, T12, T13, T14, T15
I02
Remote Start/Stop
binary
T11
I03
Remote Start And Load
binary
T11
I04
Access Lock
binary
T07, T11, T12, T13, T14, T15
I07
Estado GCB
binary
T07, T11, T12, T13, T14, T15
I10
Aviso Externo 1
binary
T07, T11, T12, T13, T14, T15
I11
Aviso Externo 2
binary
T07, T11, T12, T13, T14, T15
I12
Aviso Externo 3
binary
T07, T11, T12, T13, T14, T15
I13
Parada Externa 1
binary
T07, T11, T12, T13,T14, T15
I14
Parada Externa 2
binary
T07, T11, T12, T13, T14, T15
I15
Parada Externa 3
binary
T07, T11, T12, T13, T14, T15
I20
Bajo Nivel de Combustible
binary
T07, T11, T12, T13, T14, T15
I21
Nivel de Combustible Analog.
analog
T13, T14, T15
I22
Baja Presión de Aceite
binary
T07, T11, T12, T13, T14, T15
I23
Presión de Aceite Analog.
analog
T13, T14, T15
I24
Alta Temperatura Refrigerante
binary
T07, T11, T12, T13, T14, T15
I25
Temperatura Refrig. Analog
analog
T13, T14, T15
Dimensiones
Dimensiones de caja:118mm x108mm x40mm
Corte panel: 96mm x 96mm
AVISO!
Si no se utilize el D+, conectar este terminal al positivo de batería!
11
Not for
Reproduction

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Briggs & Stratton ComAp InteliNano NT and is the answer not in the manual?

Briggs & Stratton ComAp InteliNano NT Specifications

General IconGeneral
BrandBriggs & Stratton
ModelComAp InteliNano NT
CategoryController
LanguageEnglish

Related product manuals