3.6 Rotate the knob till the LED screen displays FEnd, then press the knob to complete and save the parameters setting
and return to normally operating status.
3.7 In parameters setting procedures, if there are no any actions taken, the signal generator will exit parameters
setting status and return to normally operating status in 10 seconds.
(*Fast output points setting methods are the same as the setting methods above.)
In Current Adjustment Mode to set current signal
Referential Code Definition (Table 1.1)
Default factory
setting value
0: Rough adjustment 1: Fine adjustment
3: Fast output mode (*must set F100>0 firstly)
0: 0-20mA 1: 4-20mA
2: 0-22mA
0: current signal display
1: 0-100.0 percentage display
2: 0-50Hz display
Add or subtract value in
rough adjustment per pulse
1 to 50: the output value changing step for
each pulse. No decimal points. Rotating the
knob one turn (360 degree) equals 20 pulses.
Can be ten times 10 x (1 to 50).
Add or subtract value in fine
adjustment per pulse
1 to 50: the output value changing step for
each pulse. No decimal points. Rotating the
knob one turn (360 degree) equals 20 pulses.
Output accuracy calibration
value
-999 to +999, 20mA±4mA. Not recommend to
set this code. if it must be set, this function is
only for professionals.
*Must adjust
output to
12mA/20mA firstly.
0: no fast output; 2—9: output points setting
Range:0-22mA, set based on user
requirements
* Before entering into F002 parameters setting status, user must rotate the knob to enter password: + - - +
Table 1.1
In Voltage Adjustment Mode to set voltage signal
Referential Code Definition (Table 1.2)
0: Rough adjustment 1: Fine adjustment
3: Fast output mode (*must set F100>0 firstly)
0: ±10V 1: ±5V 2: 0-10V 3: 2-10V; 4: 0-5V
5: 1-5V 6: 0-3.3V 7: 0-2.5V 8: 0-1V
9: -10V -0V