Starpro Max/Plus, B-Max & Compact Plus Control LCD Display Settings
20
1
2
3
4
5
6
7
ZONE / REFRIGERATION MODE (NETWORK 516 MODULE MODE AND
ON-BOARD RELAYS)
This is the selection mode for incorporating adaptive
zoning and refrigeration onto the system.
No zone or add-on refrigeration
On-board or Brivis Network or 516 Module relays
can be used for Heating only zone control (up to 3 with
on-board or 4 with Module)
On-board or Brivis Network or 516 Module relays
can be used for zone control (up to 2 on-board or 3
with Module) for Heating and Add-On refrigeration.
Brivis Network 516 zone control (up to 3), for
Heating only.
Brivis Network 516 zone control (up to 2), for
H
eating and Add-On refrigeration.
Brivis
Network 516 zone control (up to 4) for
Heating. Add-on refrigeration Control on-board.
Not available with SP4, SP5 & SP6 series heaters.
8
COOLING - ZONING MINIMUM FAN SPEED SETTING
This is the minimum RPM the fan will operate to with the maximum outlets
closed due to the Networker zoning in coding mode.
DO NOT SET BELOW 1000
-
Note: All settings are saved automatically as you leave the set up mode. To leave the set up mode and return
to normal operation, either leave the control untouched for 20 seconds, or keep pressing the SET button until the
normal operation screen resumes, or press and hold the SET button for 3 seconds.
CAAB021918I Installer's Heat_CAAB021918I 10/10/13 4:03 PM Page 23