How to troubleshoot no power on my BRONKHORST Controller?
N
nmillerSep 12, 2025
If your BRONKHORST Controller shows no power and the LEDs are not lit, the first thing to check is the power supply. Also, verify the cable connection. If these steps don't resolve the issue and you suspect an internal fuse has blown due to a prolonged short, the unit may need to be returned to the factory.
B
Brittany AllenAug 21, 2025
What to do if my BRONKHORST Controller shows maximum output signal?
M
Miss Kristina Jordan DDSAug 21, 2025
If the BRONKHORST Controller's output signal is at its maximum (131.07%), it could be due to several reasons. The flow might be too high, causing the valve to be fully open, so try closing the valve. Alternatively, for normally opened valves, the valve may be in a 'Safe State', so you should remove the cause of 'Valve Safe State'. If neither of these resolves the issue, there may be a pcb/sensor failure, requiring a return to the factory.
E
Eric LesterAug 23, 2025
Why is the output of my BRONKHORST Controller oscillating?
R
Robert RuizAug 23, 2025
If your BRONKHORST Controller's output is oscillating, the controller settings might be incorrect, specifically the PID settings may be too fast, so try decreasing the Controller Speed value. Another potential cause is that the inlet/outlet pressure is either too high or too low, so you should adjust the pressure or set the correct instrument pressure with FlowTune™. Finally, the wrong gas may be selected, so set the correct process gas with FlowTune™.
M
Matthew StokesAug 26, 2025
What to do if my BRONKHORST Controller has zero output signal?
C
Crystal BarreraAug 26, 2025
If your BRONKHORST Controller is showing a zero output signal, it could be due to several reasons. First, check if the setpoint is accepted and if the control mode is correct. If the setpoint is too low, give a setpoint >2%. If the valve is in 'Safe State' (for normally closed valves), remove the cause of 'Valve Safe State'. If none of these solves the issue, it may indicate a pcb/sensor failure or a blocked/contaminated laminar flow element, both requiring a return to the factory.
T
Theresa MaysAug 27, 2025
Why my BRONKHORST Controller setpoint cannot be achieved?
S
Sean HayesAug 27, 2025
If your BRONKHORST Controller cannot achieve the setpoint, it may be because the pressure difference across the instrument is insufficient to achieve the requested flow rate, so check the inlet/outlet pressure. Alternatively, there may be a stoppage, so remove any contamination. In some cases, the valve may be blocked or damaged, requiring a return to the factory.
R
Renee ReyesAug 29, 2025
What to do if flow signal is gradually decreasing on my BRONKHORST Controller?
B
Brenda BanksAug 30, 2025
If the flow signal of your BRONKHORST Controller is gradually decreasing without any setpoint change, it may be because the pressure difference across the instrument is insufficient to achieve the requested flow rate, so check the inlet/outlet pressure. Another possible cause is process gas condensation, in which case you should decrease the pressure or increase the gas temperature.
R
Ryan FranklinSep 1, 2025
Why does my BRONKHORST Controller have a non-zero output signal when valve is closed?
A
anthony66Sep 1, 2025
If your BRONKHORST Controller shows a non-zero output signal when the valve is closed, it could be due to a leaking valve (through the valve), so check the valve specifications for leak-tightness through the valve. It may also be due to a non-zero offset signal (which occurs at upward/downward placement at higher pressures), so see Adjusting zero point.
M
Michelle LoganSep 3, 2025
How to fix no power on BRONKHORST Measuring Instruments?
R
Richard VasquezSep 3, 2025
If your BRONKHORST Measuring Instruments show no power (LEDs are not lit), check the power supply and cable connections. If the internal fuse has blown due to a long-lasting shortage, return the device to the factory.
Y
ynelsonSep 5, 2025
What to do if setpoint cannot be achieved on BRONKHORST Measuring Instruments?
M
Mr. Jerry AdamsSep 5, 2025
If the setpoint cannot be achieved on your BRONKHORST Measuring Instruments, check the inlet and outlet pressure to ensure sufficient pressure difference across the instrument. Remove any contamination that may be causing a stoppage. If the valve is blocked or damaged, return the instrument to the factory.
J
Jerry ArnoldSep 7, 2025
Why is there a maximum output signal on BRONKHORST Measuring Instruments?
C
Cynthia HodgesSep 7, 2025
If your BRONKHORST Measuring Instruments display a maximum output signal (131.07%), it could be due to the flow being too high, causing the valve to be fully open. In this case, close the valve. If the valve is in 'Safe State' for normally open valves, remove the cause of the 'Valve Safe State'. If there is a pcb/sensor failure, return the instrument to the factory.