MINIMUM CLEARANCES
NOTE: These boilers are intended to be installed in a room which is large compared to the size of the boiler.
They are not intended for alcove installation and are suitable for installation on non-combustible flooring
only.
DIMENSION
D-SERIES F-SERIES
1
CL-SERIES K-SERIES RV, RW & AB SERIES
WATER/
STEAM
TO 50#
STEAM
OVER
50#
WATER
/STEAM
TO 50#
STEAM
OVER
50#
WATER
/STEAM
TO 50#
STEAM
OVER
50#
WATER
/STEAM
TO 50#
STEAM
OVER
50#
WATER
/STEAM
TO 50#
STEAM
OVER
50#
A 18" 36" 18" 48" 24" 24" 18" 36" 24" 24"
B 24" 24" 48" 96" 48" 36" 48" 24" 48" 48"
C
V
& C
H
18" 36" 18" 36" 24" 24" 24" 24" 24" 24"
D 48" 96" 18" 36" 24" 24" 24" 24" 24" 24"
E
L
& E
R
24" 24" 18" 36" 24" 24" 24" 24" 32" 32"
1 - F-Series boilers are approved for installation on combustible flooring. Do not install on carpeting.
A - Clearance above boiler
B - Front of boiler
C
V
- Clearance from gas vent, measured vertically above pipe
C
H
- Clearance from gas vent, measured horizontally or below pipe
D - From back of boiler
E
L
- Left side of boiler
E
R
- Right side of boiler
These clearances are general minimum clearances. Local codes may dictate larger clearances.