6
582K AHRI RATINGS
LEGEND
NOTES:
1. Rated in accordance with AHRI Standards 210/240 (04-06 size)
and 340/360 (07 size).
2. Rating are based on:
Cooling Standard: 80°F (27°C) db, 67°F (19°C) wb indoor air
temperature and 95°F (35°C) db outdoor air temperature.
IEER Standard: A measure that expresses cooling part-load EER
efficiency for commercial unitary air-conditioning and heat pump
equipment on the basis of weighted operation at various load
capacities.
3. All 582K units comply with ASHRAE 90.1-2016 (American Society
of Heating, Refrigerating, and Air-Conditioning Engineers) and
DOE-2018 (Department of Energy) Energy Standard for minimum
SEER and EER requirements.
4. 582K units comply with US Energy Policy Act (2005). To evaluate
code compliance requirements, refer to state and local codes.
559K AHRI RATINGS
LEGEND
NOTES:
1. Rated in accordance with AHRI Standards 210/240 (04-06 size)
and 340/360 (07 size).
2. Rating are based on:
Cooling Standard: 80°F (27°C) db, 67°F (19°C) wb indoor air
temperature and 95°F (35°C) db outdoor air temperature.
IEER Standard: A measure that expresses cooling part-load EER
efficiency for commercial unitary air-conditioning and heat pump
equipment on the basis of weighted operation at various load
capacities.
3. All 559K units comply with ASHRAE 90.1-2016 (American Society
of Heating, Refrigerating, and Air-Conditioning Engineers) and
DOE-2018 (Department of Energy) Energy Standard for minimum
SEER and EER requirements.
4. 559K units comply with US Energy Policy Act (2005). To evaluate
code compliance requirements, refer to state and local codes.
582K UNIT
COOLING
STAGES
NOMINAL
CAPACITY
(TONS)
NET COOLING
CAPACITY
(MBH)
TOTAL POWER
(KW)
SEER EER
IEER WITH
2-SPEED
INDOOR FAN
MOTOR
582K 04 1 3 34.5 3.0 14.0 11.5 N/A
582K 05 1 4 47.0 4.1 14.0 11.6 N/A
582K 06 1 5 58.5 5.3 14.0 11.0 N/A
582K 07 2 6 70.0 6.4 N/A 11.0 15.0
AHRI Air-Conditioning, Heating and Refrigeration Institute
EER Energy Efficiency Ratio
IEER Integrated Energy Efficiency Ratio
SEER Integrated Energy Efficiency Ratio
®
®
®
®
559K UNIT
COOLING
STAGES
NOMINAL
CAPACITY
(TONS)
NET COOLING
CAPACITY
(MBH)
TOTAL POWER
(KW)
SEER EER
IEER WITH
2-SPEED
INDOOR FAN
MOTOR
559K 04 1 3 34.4 2.9 14.0 11.7 N/A
559K 05 1 4 47.0 4.0 14.0 11.8 N/A
559K 06 1 5 58.5 5.2 14.0 11.2 N/A
559K 07 2 6 70.0 6.3 N/A 11.2 15.2
AHRI Air-Conditioning, Heating and Refrigeration Institute
EER Energy Efficiency Ratio
IEER Integrated Energy Efficiency Ratio
SEER Integrated Energy Efficiency Ratio
®
®
®
®