ELECTRICAL DATA
UNIT
S I Z E ---
VOLTAGE,
SERIES
V/PH
OPER VOLTS* COMPR FAN
MCA
MIN
WIRE
SIZE{
MIN
WIRE
SIZE{
MAX
LENGTH
ft (m)}
MAX
LENGTH
ft (m)}
MAX
FUSE*
*or
CKT
BRK
AMPS
MAX MIN LRA RLA FLA 60C 75C 60C 75C
024--- B
208---230/1 253 197
58.3 12.5 0.6 16.2 14 14 48 (14.8) 46 ( 14.1) 25
036--- B 83.0 18.5 0.6 23.7 12 12 52 (16.0) 50 ( 15.3) 40
048--- B 104.0 22.8 1.3 29.8 10 10 67 (20.4) 63 ( 19.4) 50
060--- C 152.9 28.8 1.5 37.5 8 8 82 ( 25.2) 78 (24.0) 60
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C , c o n su l t t a bl e 3 1 0 --- 1 6 o f t h e N E C ( N F PA 7 0 ) . T h e a m p a ci t y o f n o n --- m e t a l l i c --- s h e a t h e d c a b l e ( N M ) ,
trade name ROMEX, shall be that of 60_C conditions, per the NEC ( NFPA 70) Article 336---26. If other than u ncoated (no---plated), 60 or 75_C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i m e --- D e l a y f u s e .
FLA --- Fu l l L o a d A m p s
LRA --- L o c k e d R o t o r A m p s
M C A --- Minimum Circuit Amps
RLA --- RatedLoadAmps
NOTE: Control circuit is 24--- V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2010 requirements of ASHRAE Standards 90.1
SOUND POWER LEVEL (dBA)
Unit Size
--- V o l t a g e ,
Series
Standard Rating dBA
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125 250 500 1000 2000 4000 8000
024--- B
7 3 --- H i g h S t a g e 51.5 55.0 63.5 69.0 62.0 58.5 56.0
7 0 --- L o w S t a ge 51.5 55.5 63.0 66.0 62.0 59.0 54.0
036--- B
7 4 --- H i g h S t a g e 54.5 57.5 65.0 70.5 62.5 60.0 57.0
7 1 --- L o w S t a ge 54.0 57.5 63.5 66.0 61.0 60.5 55.0
048--- B
7 5 --- H i g h S t a g e 53.5 59.5 66.0 70.5 64.0 61.5 55.0
7 1 --- L o w S t a ge 54.0 59.5 66.0 66.0 63.0 61.5 55.5
060--- C
7 4 --- H i g h S t a g e 51.5 58.0 66.0 68.0 64.5 63.0 61.5
7 3 --- L o w S t a ge 53.0 58.5 66.5 68.0 64.5 63.0 58.5
NOTE: Tested in compliance with AHRI 270---2008 but not listed with AHRI.
SOUND POWER LEVEL (dBA) WITH ACCESSORY SOUNDSHIELD
Unit Size
--- V o l t a g e ,
Series
Standard Rating dBA
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125 250 500 1000 2000 4000 8000
024--- B
7 1 --- H i g h S t a g e 50.0 55.0 63.0 68.0 61.5 57.5 52.0
7 0 --- L o w S t a ge 50.5 56.0 63.0 66.0 61.5 58.0 51.5
036--- B
7 2 --- H i g h S t a g e 54.5 57.0 64.5 69.0 61.5 58.5 53.0
7 0 --- L o w S t a ge 55.5 56.5 63.0 65.0 60.5 59.0 52.0
048--- B
7 4 --- H i g h S t a g e 54.0 59.5 66.0 70.0 63.0 59.0 51.5
7 0 --- L o w S t a ge 53.5 59.0 65.5 65.0 62.5 60.5 54.0
060--- C
7 3 --- H i g h S t a g e 52.0 58.5 66.0 68.0 64.0 60.5 56.5
7 2 --- L o w S t a ge 54.0 58.0 66.0 67.5 64.0 61.0 55.0
NOTE: Tested in compliance with AHRI 270---2008 but not listed with AHRI.
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE--- VOLTAGE, SERIES REQUIRED SUBCOOLING _F(_C)
024--- B 10 ( 5.6)
036--- B 13 ( 7.2)
048--- B 12 ( 6.7)
060--- C 11 (6.1)
226A