HEAT PUMP HEATING PERFORMANCE Continued
* The Btuh heating capacity values shown are net “integrated” values from which the defrost effect has been subtracted. The Btuh heating from supplement
heaters should be added to those values to obtain total system capacity.
The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to
obtain total system kilowatts.
EDB—Entering Dry Bulb
NOTE: The performance shown includes the PressureGuard™ cycling the outdoor fan. The ambient temperature that the
outdoor fan cycles depends on the outdoor/indoor combination, indoor airflow, installation practices, and system mainte-
nance, all of which affect system performance.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
3 7 172737475767
EDB CFM
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†
650AN048-A,C Outdoor Section With FV4ANF005 Indoor Section
65
1400 18.5 17.0 2.86 22.9 21.1 2.99 27.9 25.4 3.11 33.5 29.8 3.26 40.2 36.6 3.45 48.2 48.2 3.69 53.8 53.8 4.34 53.1 53.1 4.20
1600 18.7 17.2 2.87 23.2 21.3 2.98 28.1 25.6 3.10 33.8 30.1 3.23 40.7 37.0 3.41 48.7 48.7 3.64 54.4 54.4 4.28 53.7 53.7 4.14
1800 18.9 17.4 2.89 23.4 21.5 2.99 28.4 25.9 3.10 34.1 30.3 3.23 41.0 37.3 3.40 49.1 49.1 3.63 54.9 54.9 4.26 54.1 54.1 4.12
70
1400 18.1 16.7 3.03 22.7 20.9 3.16 27.6 25.2 3.29 33.2 29.4 3.44 39.8 36.2 3.64 47.5 47.5 3.89 54.3 54.3 4.57 52.3 52.3 4.40
1600 18.4 16.9 3.03 23.0 21.1 3.15 27.8 25.4 3.27 33.5 29.7 3.41 40.2 36.5 3.60 48.0 48.0 3.83 53.6 53.6 4.50 52.9 52.9 4.33
1800 18.6 17.1 3.05 23.2 21.3 3.16 28.1 25.6 3.27 33.8 30.0 3.41 40.5 36.9 3.58 48.4 48.4 3.81 54.1 54.1 4.47 53.3 53.3 4.31
75
1400 17.7 16.3 3.19 22.4 20.6 3.33 27.4 24.9 3.48 32.8 29.2 3.64 39.3 35.7 3.84 46.8 46.8 4.09 52.2 52.2 4.80 51.4 51.4 4.62
1600 18.0 16.6 3.20 22.7 20.9 3.33 27.6 25.2 3.46 33.1 29.4 3.60 39.7 36.1 3.79 47.4 47.4 4.04 52.8 52.8 4.72 52.0 52.0 4.54
1800 18.2 16.8 3.22 22.9 21.1 3.33 27.8 25.4 3.45 33.4 29.7 3.59 40.0 36.4 3.77 47.8 47.8 4.01 53.3 53.3 4.69 52.5 52.5 4.51
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling
Indoor
Section Size
Cooling
Capacity Power Capacity Power
FV4ANF 005 1.00 1.00 FX4ANB 060 1.01 1.02
F(A,B)4AN(F,B,C) 060 1.02 1.10 FX4ANF 048 1.01 1.06
FB4ANB 070 1.01 1.02 CE3AA 060 1.01 1.06
FC4BN(F,B) 060 1.01 1.09 CJ5A/CK5A/CK5BA 060 1.01 1.03
FC4BNB 070 1.01 1.02 CJ5A/CK5A/CK5BN 060 1.02 1.04
FK4CNB 006 1.01 0.96 CJ5A/CK5A/CK5BX 060 1.02 1.04
FK4CNF 005 1.01 1.01 CK3BA 060 1.01 1.03
FV4ANB 006 1.01 0.96
650AN060-B,C Outdoor Section With FV4ANB006 Indoor Section
65
1750 24.4 22.4 3.73 30.9 28.4 3.88 37.9 34.6 4.05 45.0 40.0 4.24 52.6 47.9 4.45 60.8 60.8 4.68 58.2 58.2 4.52 56.3 56.3 4.47
2000 24.9 22.9 3.76 31.5 28.9 3.90 38.5 35.1 4.05 45.7 40.6 4.22 53.2 48.4 4.41 61.6 61.6 4.61 59.0 59.0 4.44 57.1 57.1 4.37
2250 25.3 23.3 3.80 31.9 29.3 3.93 39.0 35.5 4.06 46.2 41.0 4.23 53.7 48.9 4.39 62.2 62.2 4.58 59.6 59.6 4.39 57.8 57.8 4.31
70
1750 23.4 21.5 3.92 30.0 27.6 4.09 37.0 33.7 4.27 44.2 39.2 4.46 52.0 47.3 4.70 60.0 60.0 4.94 57.4 57.4 4.76 55.4 55.4 4.71
2000 23.8 21.9 3.95 30.5 28.0 4.10 37.6 34.3 4.26 44.8 39.8 4.44 52.5 47.8 4.65 60.7 60.7 4.87 58.1 58.1 4.67 56.2 56.2 4.60
2250 24.3 22.3 4.00 31.0 28.5 4.13 38.1 34.7 4.28 45.4 40.3 4.45 53.1 48.3 4.63 61.4 61.4 4.83 58.8 58.8 4.62 56.9 56.9 4.53
75
1750 22.2 20.5 4.12 28.9 26.6 4.30 36.0 32.9 4.49 43.2 38.4 4.70 51.3 46.7 4.96 59.2 59.2 5.21 56.5 56.5 5.02 54.5 54.5 4.95
2000 22.7 20.9 4.15 29.5 27.1 4.31 36.7 33.4 4.49 43.9 39.0 4.67 51.9 47.2 4.90 59.9 59.9 5.13 57.3 57.3 4.92 55.3 55.3 4.83
2250 23.2 21.3 4.20 30.0 27.5 4.34 37.2 33.9 4.50 44.5 39.5 4.67 52.4 47.7 4.88 60.6 60.6 5.09 57.9 57.9 4.86 56.0 56.0 4.76
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling
Indoor
Section Size
Cooling
Capacity Power Capacity Power
FV4ANB 006 1.00 1.00 FX4ANB 060 1.00 1.03
FB4ANB 070 1.00 1.03 CC5A/CD5AW 060 0.98 1.06
FC4BNB 070 1.00 1.03 CJ5A/CK5A/CK5BX 060 0.98 1.02
FK4CNB 006 0.99 0.99