Regulator-actuator replacement/rotation
11
In case of replacement of the regulator-actuator it is necessary to remove all electric connections and perform the following operations:
NOTE: Following the above operations, perform the zero and full scale acquisition.
Thermostatic function
In case of motor failure or power failure, the device is able to guarantee the temperature adjustment through the thermostatic element. To ensure
thermostatic adjustment, perform the following operations:
- Screw up to stop (clockwise)
- Make a reference
- Adjust the desired set point reading the temperature using suitable instruments (make a maximum of 1 turn)
It is possible to temporarily perform the disinfection/thermal shock turning over one turn, disabling the thermostatic control.
max 360° 35–65°C
Max 4 N
m