Wall-mounted compact indirect heat interface unit
SATK30 series
INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE
CONTENTS
Safety instructions
Dimensions
Technical specifications
Installation
Commissioning
Electronic regulator
SATK30103HE
SATK30105HE
Electric connections
Safety and alarms
Troubleshooting
2
3
4
6
7
9
10
11
12
13
Maintenance
14
Function
The SATK series HIU allows independent control of heat regulation and
domestic hot water production within centralised heating systems or
served by district heating networks.
Product range
SATK30103HE Indirect wall-mounted compact HIU for
instantaneous domestic hot water production,
power capacity 40 kW.
SATK30105HE Indirect wall-mounted compact HIU for
instantaneous domestic hot water production,
power capacity 65 kW.
78232.01EN
www.caleffi.com
Commissioning checklist
16
Operating cycles
8

Questions and Answers

  • M
    Marcia BrewerAug 17, 2025
    What to do if hot water flow rate is insufficient in CALEFFI Recording Equipment?
    • S
      Sarah AtkinsonAug 17, 2025
      If the hot water flow rate is insufficient, check if: * The domestic water system shut-off valves are partially or completely closed; if so, open the valves. * For other potential causes such as a clogged HIU strainer, insufficient centralised domestic circuit cold water flow rate, no cold water in centralised domestic circuit, or a completely clogged HIU strainer, it is recommended to call qualified personnel to have it serviced.
  • A
    Anthony DayAug 23, 2025
    Why is the hot water temperature too high in my CALEFFI Recording Equipment?
    • K
      Kathy NicholsonAug 23, 2025
      If the hot water temperature is too high, consider the following: * Decrease the domestic water cycle temperature set point. * Restore the correct connection if the DHW temperature probe cable is inverted with the heating probe. * For other potential causes such as a faulty modulating valve actuator, a valve obturator blocked in intermediate or open position, a non-working electronic controller, or excessive pressure in the primary circuit, it is recommended to call qualified personnel to have it replaced or serviced. If there is excessive pressure in the primary circuit, contact the person in charge of the system.
  • Q
    qjonesAug 27, 2025
    What to do if CALEFFI SATK30 start-up triggers the safety circuit breaker?
    • E
      Elizabeth JacobsonAug 27, 2025
      If the start-up of the heat interface unit heating function triggers the safety circuit breaker, check that the pump cable connector is inserted the right way round.
  • B
    Brenda BeasleyNov 1, 2025
    How to fix CALEFFI SATK30 when water is not heated?
    • E
      erikreedNov 2, 2025
      If the water is not heated, check the following: * Ensure the primary circuit shut-off valves are open. * Reconnect the modulating valve actuator connector if it's disconnected. * Reconnect the modulating valve actuator if it's disconnected from the valve body. * Restore the correct connection if the DHW temperature probe cable is inverted with the heating probe. * Vent the system to remove any air. * Reconnect the DHW temperature probe if disconnected. * Restore the correct switch setting if it's incorrect. * Reconnect the DHW priority flow meter if disconnected. * Restore the HIU electric supply if there is no electric power. * For other potential causes such as a faulty modulating valve actuator, a non-working electronic controller, a blocked valve obturator, a faul...
  • J
    Jason BallNov 7, 2025
    What to do if CALEFFI SATK30 room is not reaching desired temperature?
    • K
      kburnsNov 7, 2025
      If the room is not reaching the desired temperature, consider the following: * Increase the heating cycle temperature set point. * Check the programming of the chrono-thermostat for incorrect temperature or time settings. * Reconnect the modulating valve actuator connector if disconnected. * Restore the correct connection if the DHW temperature probe cable is inverted with the heating probe. * Vent the system to remove any air. * Restore the pump cable connection if it's not connected. * Open any closed system shut-off valves/terminals. * Restore HIU electric supply if there is no electric power. * Restore system pressure if the heating circuit pressure is too low. * Restore correct switch setting if it's incorrect. * For other potential causes such as a clogged HIU ...
  • E
    Erin MillerNov 11, 2025
    Why CALEFFI Recording Equipment water is hot but not reaching desired temperature?
    • S
      Stephanie StuartNov 11, 2025
      If the water is hot but not reaching the desired temperature, consider these potential causes: * Increase the domestic water cycle temperature set point. * Reconnect the modulating valve actuator connector if it is disconnected. * Restore the correct connection if the DHW temperature probe cable is inverted with the heating probe. * Decrease the demand if there is excessive demand for DHW. * For other potential causes such as a clogged primary circuit strainer of the HIU, a partly clogged heat exchanger, a faulty modulating valve actuator, a valve obturator blocked in intermediate position, a non-working electronic controller, insufficient centralised system temperature, or insufficient primary circuit flow rate, it is recommended to call qualified personnel to have it serviced ...

Summary

Safety Instructions

General Warnings

General warnings about installation and maintenance hazards.

Electrical Hazard Warnings

Specific warnings regarding electrical hazards and safety precautions.

Installation Procedures

Main Electrical Connection

Electrical connection guidelines for the main supply.

Electrical System Safety

General advice on electrical system compatibility and safety.

Commissioning Process

Central Heating System Filling

Procedure for filling and venting the central heating system.

User System Filling

Steps for filling the user system, including pressure adjustments.

System Start-Up

Final checks and activation of the HIU after installation.

Electronic Regulator Overview

Safety and Alarm Codes

Heating Circuit Pressure Switch Fault

Fault code 4: Heating circuit pressure switch fault and its resolution.

Safety Thermostat Cut-Out

Fault code 69: Safety thermostat activation and how to reset.

Heating Probe Fault

Fault code 5: Heating probe failure and remedy.

Domestic Water Probe Fault

Fault code 6: DHW probe failure and remedy.

Compensation Probe Fault

Fault code 15: Compensation probe failure and remedy.

SATK30103 HE Model Details

SATK30103 HE Factory Settings

Default factory settings and instructions to modify them for different temperature ranges.

Maintenance Procedures

Electric Connections Guide

Troubleshooting Common Issues

Water Not Heated

Troubleshooting steps for when the unit does not heat water.

Heating Function Troubleshooting

Safety Circuit Breaker Tripping

Diagnosing issues related to safety circuit breaker tripping during heating start-up.

Commissioning Checklist

CALEFFI SATK30 Series Specifications

General IconGeneral