In easy split models the algorithm for managing the door depends on
the type of unit selected, according to parameter Ado, and the setting
of parameter A4.
Ado = 0: display case
Opening the door:
When opening the door, if parameter A7 or d8 ≠0, the controller goes
into pre-alarm status:
• the temperature displayed and the alarm icon (bell) ash;
• the high temperature alarm is disabled;
• if A4=7, 10 the fan is stopped;
• if A4=8, 11 the fan and the compressor are stopped;
• if A4=10, 11 and if the light output is con gured (H1=4), the light is
on.
If the door remains open for a time greater than A7, the controller goes
into alarm status:
• the temperature displayed ashes alternating with ‘dor’;
• the buzzer is activated;
• the light remains on if an output is con gured as the light output
(H1=4);
• the high temperature alarm is enabled, after the delay Ad;
• the auxiliary relay is activated if H1 = 3;
• the fan is ON;
• if A4=8, 11 the compressor is restarted, observing any protection times
(‘c’ parameters);
Closing the door:
The controller resumes normal operation:
• the fans and the compressor are started if called (observing any
protection times – ‘c’ parameters)
• the light is switched o if an output is con gured as the light output
(H1= 4);
• the auxiliary relay is deactivated if H1 = 3;
• the buzzer is deactivated;
• the temperature stops ashing and the alarm icon (bell) goes o ;
• the high temperature alarm is enabled after the delay Ad.
Ado = 1: cold room
Assuming the user enters the cold room, closing the door behind him,
and then exits the room, closing the door a second time. If the user
enters the cold room and then leaves immediately, closing the door, the
controller waits until the door is opened a second time and if this does
not occur within a certain time (A7 or d8), normal operation resumes.
Opening the door the rst time:
When opening the door, if parameters A7 and d8 are≠0, the controller
goes into pre-alarm status:
• the temperature displayed and the alarm icon (bell) ash;
• the high temperature alarm is disabled;
• if A4=7, 10 the fan is stopped;
• if A4=8, 11 the fan and the compressor are stopped;
• if A4=10, 11 and if the light output is con gured (H1=4), the light is
activated;
If the door remains open for a time greater than A7, the controller goes
into alarm status:
• the fans and compressor are started if called; when restarting the
compressor the protection times are observed (‘c’ parameters);
• the light remains on if an output is con gured as the light output (H1=
4);
• the auxiliary relay is energised if H1 = 3;
• the temperature displayed ashes alternating with ‘dor’;
• the buzzer is activated;
• the high temperature alarm is enabled after the delay Ad.
Closing the door the rst time:
the controller maintains the previous status:
• the fans and/or compressor (see parameter ‘A4’) remain o ;
• the light is kept on if an output is con gured as the light output (H1
= 4);
• the temperature and the alarm icon (bell) ash;
• the high temperature alarms remains disabled.
If, after rst closing, the door remains closed for a time greater than A7,
the controller resumes normal operation:
• the fans and/or compressors are switched on if called; when the
compressor restarts the protection times must be observed (‘c’
parameters)
• the light remains on if an output is con gured as the light output (H1
= 4);
• the high temperature alarm is enabled after the delay Ad;
• the temperature stops ashing and the alarm icon (bell) goes o .
Note: assuming the user has already left the cold room, and in
that case will be able to turn o the light from the outside by
pressing the DOWN button, or alternatively is still working inside.
If, after rst closing, the light is switched o manually (the user is outside
the cold room), the controller resumes normal operation without waiting
for the door to open a second time:
• the fans and/or compressors are switched on if called; when the
compressor restarts the protection times must be observed (‘c’
parameters);
• the high temperature alarm is enabled after the delay Ad;
• the temperature stops ashing and the alarm icon (bell) goes o .
Opening the door the second time: status unchanged.
Closing the door the second time:
• the fans and/or compressors are switched on if called; when the
compressor restarts the protection times must be observed (‘c’
parameters)
• the high temperature alarm is enabled after the delay Ad;
• the light is o if an output is con gured as the light output (H1= 4).