2.3 DEFAULT VALUES
The factory-set configuration provides for the following devices:
- ambient temperature probe
- ambient relative humidity probe
- outside air temperature probe
- water temperature probe
- cold water valve
- hot water valve
- all heaters enabled (n.2)
- both compressors enabled
- external humidifier
Here is the list of the default values the controller accepts as machine parameters
whenever the user answers affirmatively to the mask successive to that of back-up
memory deletion in the “special procedures” branch.
SELECTABLE PARAMETERS RANGE PRE-SET
Temperature set-point 15÷30 23.0º
Temperature differential 1÷10
High temperature threshold 10÷50 30º
Low temperature threshold 0÷30 10º
Integration constant **** 600 sec
Only 1 compressor enabled;
Set-point compressor 1 in CW 0÷100% 50%
Hysteresis compressor 1 in CW 0÷100% 50%
or;
Set-point compressor 1 in ES 0÷100% 66%
Hysteresis compressor 1 in ES 0÷100% 33%
Both compressors enabled;
Set-point compressor 1 in CW 0÷100% 25%
Hysteresis compressor 1 in CW 0÷100% 25%
Set-point compressor 2 in CW 0÷100% 75%
Hysteresis compressor 2 in CW 0÷100% 25%
or;
Set-point compressor 1 in ES 0÷100% 49%
Hysteresis compressor 1 in ES 0÷100% 16%
Set-point compressor 2 in ES 0÷100% 82%
Hysteresis compressor 2 in ES 0÷100% 16%
1 heater enabled;
Set-point (not modifiable) 0÷100% 25%
Hysteresis (not modifiable) 0÷100% 25%
2 heaters enabled;
Set-point heater 1 (not modifiable) 0÷100% 25%
Hysteresis heater 1 (not modifiable) 0÷100% 25%
Set-point heater 2 (not modifiable) 0÷100% 75%
Hysteresis heater 2 (not modifiable) 0÷100% 25%
Beginning cold water valve 0÷100% 0%
End cold water valve 0÷100% 100%
Beginning hot water valve 0÷100% 0%
End hot water valve 0÷100% 100%
Set-point relative humidity 0÷100UR% 50%
Humidity differential 5÷20%UR 10%
High humidity threshold 0÷100% 80%
Low humidity threshold 0÷100% 30%
Set-point dehumidification step 0÷100% 50%