pCOWeb +030220966 – rel. 1.1 – 12.12.2017 56
9.12 pCO APPLICATION UPDATE
pCOWeb is able to update the pCO application of every type of pCO controller.
To update the pCO application, when one of Carel or Modbus protocol is running, the process just needs a zipped file where the needed files are present.
pCOWeb supports:
• BLB, BIN, BLX (strategy)
• IUP (user interface)
• GRP or GRT (graphic resources, not both at the same time)
• DEV (default parameters)
• PVT, LCT (bios logger configuration)
pCOWeb does not support:
• BIOS
• BOOT
Figure 9.ee - pCO application zip file selection
The pCO must have a bios version >=4.10 installed (4.20 recommended). As starting from this specific versions of bios the pCO switches automatically to
Winload protocol (SERIAL1_PROTOCOL=4 or BMS_PROTOCOL = 4) as soon as the pCOWeb sends a specific command.
Then, a report of the application upload is shown, as below. The user can choose to proceed with the operation or to abort it.
Figure 9.ff - pCO application zip file selection