pCOWeb +030220966 – rel. 1.1 – 12.12.2017 57
In case the operation is launched, the following report is shown.
Figure 9.gg - Flash image upload report
VERY IMPORTANT
It is standard in custom pCO application and in each Carel standard application that, in order to avoid memory mismatching, to re-initialize the unit to the
default configuration when the application updates, so that is strongly advised to upload, together with the applications' files, a consistent DEV file for the
specific application (i.e. downloading it from another controller with similar configuration and the new software).
Updating the pCO application is a very critical procedure for the unit, it implies to switch it off before taking any action, pCO will de-energize every digital and
analog output during the firmware upgrade without taking in consideration any safety timing or specific procedure defined in the software.
Please, go to http://ksa.carel.com/ and download the step by step guide “Updating pCO Application via pCOWeb.pdf”
10 TECHNICAL SPECIFICATIONS
CPU: ARM Cortex-A7, clock up to 528 MHz
Memory: 256 MB RAM, 4 GB FLASH (around 3.2 GB available for web pages and user data).
Operating system: GNU/LINUX 4.11.12 – file system for the non-volatile user memory: F2FS
Firmware A2.0.4 – B2.0.4
Ethernet interface: RJ45 connector for 10/100BaseT full duplex Ethernet;
use a class 5 shielded cable, max 100 m.
Protocols managed: HTTP (thttpd 2.27)
SMTP (msmtp 1.6.5)
DHCP (dhcpcd 6.11.5)
FTP (server: inetutils 1.9.4; client: ncftp 3.2.6)
SSH/SCP (openssl 1.0.2k, openssh 7.5p1)
DNS
SNMP v1 (Net-SNMP 5.7.3)
SNMP v2c (Net-SNMP 5.7.3)
BACnet Ethernet ISO8802-2/8802-3
BACnet/IP (135-2004 Addendum A/Annex J)
MODBus TCP/IP (libfreemodbus 1.5.0)
Operating conditions: -40T70 °C, <90% RH non-condensing
Storage conditions: -40T70 °C, <90% RH non-condensing
Environmental pollution: 2
CAREL order code: PCO1ØØØWDØ7