7(&+1,&$/63(&,),&$7,216
PRGHOV 3-6 3-; 3-< 3-&
32:(56833/<
very low voltage
12Vac ±10%, 50/60Hz / 12Vdc (11÷16Vdc) • • • •
230Vac/Vdc, +10/-15%, 50/60Hz
• • • •
low voltage
115Vac/Vdc, +10/-15%, 50/60Hz
• • • •
UDWHGSRZHU9$
3
DFFXUDF\ZLWKUHIHUHQFHWRWKHW\SHRISUREHV
Carel NTC (°C) ±1
PTC (°C) ±3
W\SHRIFRQWUROSUREH
Carel NTC (10 K at 25°C) • • • •
PTC (985 Ω at 25ºC) •
W\SHRIGHIURVWSUREH
Carel NTC (10 K at 25°C)
• •
PTC (985 Ω at 25 ºC)
control range:-50÷90 °C (-50 ÷127 °F)
• • • •
operating conditions: -10÷50 °C, <80% RH
• • • •
storage conditions:-20÷70 °C, <80% RH
• • • •
86(5,17(5)$&(
2 and ½ digit LED display
• • • •
buzzer signal to indicate:
•
compressor ON (*)
7RS(FR 7RS(FR
7RS(FR
7RS(FR
defrost ON
7RS
7RS
7RS
7RS
continuous cycle ON
7RS(FR 7RS(FR
7RS(FR
7RS(FR
alarm event
7RS
7RS
7RS
7RS
VSHFLDOIXQFWLRQV
duty setting
• • • •
continuous cycle
• • • •
Multifunction input
• •
Multifunction output for alarm relay
• • •
serial connection
7RS
7RS
7RS
7RS
keypad protection
• • • •
SURJUDPPLQJ
• • • •
0(&+$1,&$/63(&,),&$7,216
dimensions (mm): 36x81x65
• • • •
clip-on fastening using bracket
• • • •
fastening from front panel using screws
7RS
7RS
7RS
7RS
type of environmental pollution: normal
• • • •
(/(&75,&$/63(&,),&$7,216
relay outputs: action type 1C
• • • •
index of protection IP54 for panel mounting
• • • •
connections: screw terminals for cables with min 0.5 mm
2
and max 1.5 mm
2
cross-section, and up to 2.5 mm
2
for crimping terminals
7RS
7RS
7RS
7RS
UL approval classification: 250Vac 12/8/5A res. 5/2/1FLA 30/12/6LRA
EN60730-1 classification: 12(2)/6(2)/5(1) AT 250Vac
48$/,7<$1'$&&85$&<
watch dog (self-checking of internal functions)
• • • •
7DE
(*): only the
7RS
versions feature the LED signals behind the buttons, the other (
(FR
) versions feature only the compressor ON
signal using the decimal point of the right-most digit.