pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index Display description Description Default UOM Values
A.Unit status
Aa01
(display only)
Pressure Suction pressure (line 1) --- … (**)
Sat.temp. Saturated suction temperature (line 1) --- … (**)
Act.setpoint Eff ective set point for pressure control (with compensation applied, line 1) … (**) … (**)
Diff erential Control diff erential for pressure control (line 1) … (**) … (**)
Aa02
(display only)
Pressure Suction pressure (line 1) --- … (**)
Sat.temp. Saturated suction temperature (line 1) --- … (**)
Act.setpoint Eff ective set point for temperature control (with compensation applied, line
1)
… (**) … (**)
Diff erential Control diff erential for temperature control (line 1) … (**) … (**)
Aa03
(display only)
Actual/req. Capacity delivered/capacity required for suction line (line 1) --- % 0/0 …100/100
Reg.status
Control status (according to the type of control set, line 1) --- --- Stop Increas
Decrease
Standby
Operating
Timings
Alarms
Reg.type Compressor control type (line 1) Neutral
zone
--- Proportional band
Neutral zone
Setpoint Eff ective suction pressure set point (with compensation applied, line 1) … (**) … (**)
Aa04
(display only)
C01, C02, …C12 Time remaining to next compressor start (line 1) --- s 0…32000
C01 Capacity delivered by compressor 1 on line 1 (a ''!'' to the right of the value
means that some form of compressor capacity override is active, e.g. times,
alarms, start-up procedure)
--- % 0…100
……
C12 Capacity delivered by compressor 12 (line 1) --- % 0…100
Aa05
(display only)
Temperature Suction temperature (line 1) --- … (**)
Superheat Superheat (line 1) --- … (**)
Aa11
(display only)
Disch.1 Discharge temperature, compressor 1 (line 1) --- … (**)
……
Disch.6 Discharge temperature, compressor 6 (line 1) --- … (**)
Aa13
(display only)
Liq.inj.1: DO Number of digital output associated and status of liquid injection/
economizer (*) compressor 1 (line 1)
--- 0…29 ON / OFF
……
Liq.inj.6: DO Number of digital output associated and status of liquid injection/
economizer (*) compressor 6 (line 1)
--- 0…29 ON / OFF
Aa15
(display only)
Discharge temperature Digital ScrollTM compressor discharge temperature (line 1) --- … (**)
Cap.reduction Digital ScrollTM compressor capacity reduction in progress (line 1) NO / YES
Oil sump temp. Digital ScrollTM compressor oil sump temperature (line 1) --- … (**)
Oil status Digital ScrollTM compressor oil dilution status (line 1) Ok
Dilute
Aa16
(display only)
Status Digital ScrollTM compressor operating status (line 1) --- --- O
Start up
On
Alarm
Off by time
On by time
Mod. manual
In pump down
Countdown Digital ScrollTM compressor time count (line 1) --- s 0…999
Compr. Digital ScrollTM compressor status (line 1) --- --- OFF
ON
Valve Digital ScrollTM valve status(line 1) --- --- OFF
ON
Requested cap. Digital ScrollTM compressor capacity required (line 1) --- % 0…100
Current capac. Digital ScrollTM compressor eff ective capacity (line 1) --- % 0…100
Aa20
(display only)
Pressure Condensing pressure (line 1) --- … (**)
Sat.temp. Saturated condensing temperature (line 1) --- … (**)
Act.setpoint Eff ective set point for pressure control (with compensation applied, line 1) … (**) … (**)
Diff erential Control diff erential for pressure control (line 1) … (**) … (**)
Aa21
(display only)
Pressure Condensing pressure (line 1) --- … (**)
Sat.temp. Saturated condensing temperature (line 1) --- … (**)
Act.setpoint Eff ective set point for temperature control (with compensation applied, line 1) … (**) … (**)
Diff erential Control diff
erential for temperature control (line 1) … (**) … (**)
Aa22
(display only)
Actual/req. Capacity delivered/capacity required for condenser line (line 1) --- % 0/0 …100/100
Status Control status (according to the type of control set, line 1) --- --- Stop
Increase
Decrease
Stand-by
Operating
Timings
Alarms
Reg.type Condenser control type (line 1) Neutral
zone
--- Proportional band
Neutral zone
Setpoint Condenser control eff ective set point (with compensation applied, line 1) … (**) … (**)
Aa23
(display only)
F1 Power output of fan 1 on line 1 (a ''!'' to the right of the value means that
some form of power override is active)
--- % 0…100
……
F8 Power output of fan 8 on line 1 (a ''!'' to the right of the value means that
some form of power override is active)
--- % 0…100
Aa24
(display only)
F9 Power output of fan 9 on line 1 (a ''!'' to the right of the value means that
some form of power override is active)
--- % 0…100
……
F16 Power output of fan 16 on line 1 (a ''!'' to the right of the value means that
some form of power override is active)
--- % 0…100
Aa25
(display only)
Discharge temperature Discharge temperature (line 1) --- … (**)
External temperature Outside temperature (line 1) --- … (**)
Aa31 (display
only)
Pressure Suction pressure (line 2) --- … (**)
Sat.temp. Saturated suction temperature (line 2) --- … (**)
Act.setpoint Eff ective set point for pressure control (with compensation applied, line 2) … (**) … (**)
Diff erential Control diff erential for pressure control (line 2) … (**) … (**)
Aa32
(display only)
Pressure Suction pressure (line 2) --- … (**)
Sat.temp. Saturated suction temperature (line 2) --- … (**)
Act.setpoint Eff ective set point for temperature control (with compensation applied, line 2) … (**) … (**)
Diff erential Control diff erential for temperature control (line 2) … (**) … (**)