Tech Support (800) 989-2275 www.carlincombustion.com
Model 60200 CAD Cell Oil
Primary Control Data Sheet
• Oil Pump Bleed Assist
60 seconds
• CAD Cell Resistance Monitoring Jack
Works with any multimeter
• Recycle on Flame Failure
• Serviceman Reset Protection
Latch-up after 3 consecutive lockouts
• Diagnostic LEDs
Status, lockout, ame
• 15-second, 30-second TFI
• Increased Flame Accuracy
• Thermostat/Aquastat Compatible
• Improved SMC Technology
Zero bleed voltage during standby
• Works Well with Generators
Insensitive to frequency changes
• Early Spark Termination (optional)
• Alarm Contacts
• Flame Signal Test Jack
Power input (red/white wire) 120 VAC, 60 HZ, 9VA
Limit circuit input (black wire) 120 VAC, 60 HZ
Motor load
10 FLA / 60 LRA
Ignitor load
120 VAC, 60 HZ, 500 VA
Valve load
120 VAC, 60 HZ, 2.0 A
Alarm contacts
24 V, AC/DC, 2A
Nozzle Line Heater
120 VAC, 60 HZ, 1 amp
Operating temperature limits
+32°F to +140°F
Storage temperature limits
-40°F to +185°F
Thermostat anticipator current
0.1 A, AC
CAD cell resistance (with flame) R < 1500 OHMS
Agencies
UL recognized (US & Canada)
Installing and Wiring
The 60200 control must be installed and serviced only by a qualified service technician.
1. Always disconnect power source before wiring to avoid electrical shock or damage to the control. All wiring must comply with
applicable codes and ordinances.
2. Thermostat terminals (T-T) provide a current source. Never apply external power to these terminals under any circumstances.
3. Alarm terminals provide a 24 VAC/VDC-rated dry contact.
Mounting
• The control may be mounted on a 4" x 4" junction box in any convenient location on the burner, furnace or wall. The location
must not exceed the ambient temperature limit, 140°F.
Wiring
• Wiring must comply with local and national electrical codes, and with the wiring diagram.
• Individual or bundled neutrals may be attached to any L2 terminal.
Field checks
1. Safety timing (TFI) test – Remove one CAD cell wire (F-F). Start burner. The control should lockout within the TFI time limit.
Replace CAD cell wire.
2. Flame failure test – Start burner. After ame is established (after TFI period), close the oil supply hand valve. This will cause a
flame failure sequence as described in the Startup & Operation section of this Data sheet. The control should recycle (restart after
65 seconds).
3. If control does not operate as described, check the wiring.
SEE WIRING DIAGRAM ON NEXT PAGE
Startup & Operation
Do not start the burner if the combustion chamber
contains oil or oil vapor.
Per UL requirements, the control will not turn on if the
CAD cell senses ame during the self-test. If the CAD cell sees light (ame) at the beginning of a cycle, the control will remain in
self-test mode until the CAD cell no longer senses light (flame). The amber LED will blink momentarily
every 3 to 4 seconds and
green LED will be on or flashing.
Model 60200 Diagnostic LEDs
– Amber OFF – Amber ON – Amber FLASHING
– Green OFF – Green ON – Green FLASHING
– Red OFF – Red ON – Red FLASHING