19
Table 3 — 09DK Electrical Data
60 HERTZ
50 HERTZ
UNIT
09DK
UNIT FAN MOTORS CONTROL CIRCUIT
Volts -3 Ph
Supplied Volts
MCA
MOCP
(Fuse)
No. FLA (ea) Volts -1 Ph Amps
Min Max
020
500 208/230 187 254 14.8 20
2
6.6 115
7
200 380 342 418 8.8 15 3.9 220
600 460 414 508 7.4 15 3.3 115
100 575 518 632 7.6 15 3.4 115
024
500 208/230 187 254 14.8 20 6.6 115
200 380 342 418 8.8 15 3.9 220
600 460 414 508 7.0 15 3.3 115
100 575 518 632 7.6 15 3.4 115
028
500 208/230 187 254 13.9 20 6.6 115
200 380 342 418 8.8 15 3.9 220
600 460 414 508 7.4 15 3.3 115
100 575 518 632 7.6 15 3.4 115
034
500 208/230 187 254 21.4 25
3
6.2 115
200 380 342 418 12.7 20 3.9 220
600 460 414 508 10.7 15 3.3 115
100 575 518 632 11.0 15 3.4 115
044
500 208/230 187 254 20.1 25 6.6 115
200 380 342 418 12.7 20 3.9 220
600 460 414 508 10.1 15 3.3 115
100 575 518 632 11.0 15 3.4 115
UNIT
09DK
UNIT FAN MOTORS CONTROL CIRCUIT
Volts -3 Ph
Supplied Volts
MCA
MOCP
(Fuse)
No. FLA (ea) Volts -1 Ph Amps
Min Max
024
800 230 207 254 14.4 20
2
6.4 230
7
900 400 342 440 6.7 15 3.0 230
028
800 230 207 254 14.4 20 6.4 230
900 400 342 440 6.7 15 3.0 230
034
800 230 207 254 20.8 30
3
6.4 230
900 400 342 440 9.7 15 3.0 230
044
800 230 207 254 20.8 30 6.4 230
900 400 342 440 9.7 15 3.0 230
FLA — Full Load Amps
MCA — Minimum Circuit Amps (for wire sizing). Complies with
NEC (National Electrical Code, U.S.A.) Section 430-24.
MOCP — Maximum Overcurrent Protective Device (Amps).
Fig. 21 — Wiring Diagram, Power Schematic; 09DK020-044
FC — Fan Contactor
FM — Fan Motor
TB — Terminal Block Connection
Terminal Block Connection
Marked Terminal
Unmarked Terminal
Splice
Factory Wire
Field Control Wiring
Field Power Wiring
LEGEND